Load connection with 3KC6 transfer switching equipment

In the case of 3KC6 transfer switching equipment, the load connection is already determined by the internally wired connection to the control unit and to the motor operator.

If the 3KC6 transfer switching equipment is mounted with the motor operator on the right, the main circuit must be connected at the bottom. This is due to the internally wired connection to the control unit and to the motor operator.
The neutral conductor must also be connected to the main terminals on either the right or the left.

98609610891_Thumbnail.png
Arrangement for load connection with 3KC6 transfer switching equipment, motor operator on the right

If the main circuit connection must be made on top, the 3KC6 transfer switching equipment must be rotated such that the motor operator is on the left.

98609987211_Thumbnail.png
Arrangement for load connection with 3KC6 transfer switching equipment, motor operator on the left
98609610891.png
98609987211.png