How do unmanaged IE switches behave with regard to LLDP messages for topology identification?

  • Entry
  • Associated product(s)
It is important to know the actual topology of a plant for diagnostics and maintenance. The topology identification is done through LLDP messages that are sent independently by PROFINET IO devices.

Unmanaged IE switches do not send LLDP messages themselves and block those from their partners. However, there are exceptions.

Table 1 shows the behavior of unmanaged IE switches.
   

Unmanaged IE SwitchArticle numberBehavior with LLDP messages
SCALANCE X-000

6GK5005-0BA10-1AA3
6GK5005-0BA10-1CA3

Blocking
6GK5005-0BA00-1AA3
6GK5005-0BA00-1CA3

Forwarding

SCALANCE XB-000

6GK5004-1GL00-1AB2 hardware release 3 and higher
6GK5004-1GL10-1AB2
6GK5004-1GM00-1AB2 hardware release 3 and higher
6GK5004-1GM10-1AB2
6GK5004-1BD00-1AB2 hardware release 4 and higher
6GK5004-1BF00-1AB2 hardware release 4 and higher
6GK5004-2BD00-1AB2
6GK5005-0GA00-1AB2 hardware release 3 and higher
6GK5005-0GA10-1AB2
6GK5005-0BA00-1AB2 hardware release 4 and higher
6GK5008-0GA00-1AB2 hardware release 3 and higher
6GK5008-0GA10-1AB2
6GK5008-0BA10-1AB2
6GK5008-0BA00-1AB2 hardware release 3 and higher

Blocking
SCALANCE X-100

6GK5108-2BB00-2AB2
6GK5108-2BD00-2AB2
6GK5112-0BA00-2AB2
6GK5116-0BA00-2AB2
6GK5124-0BA00-2AB2
6GK5106-2BB00-2AC2
6GK5106-2BD00-2AC2
6GK5108-0BA00-2AC2
6GK5116-0BA00-2AC2
6GK5124-0BA00-2AC2
6GK5124-0BA00-2AR3
6GK5124-0BA00-3AR3

Blocking
6GK5104-2BB00-2AA3
6GK5106-1BB00-2AA3
6GK5108-0BA00-2AA3
6GK5112-2BB00-2AA3
6GK5116-0BA00-2AA3
6GK5124-0BA00-2AA3
Forwarding
SCALANCE X-101
Media converters

6GK5101-1BB00-2AA3
6GK5101-1BC00-2AA3 

Forwarding (media converters should be transparent)

Table 1

All unmanaged IE switches that forward LLDP messages may not be included in the topology identification of STEP 7. According to the configuration these are available, but because they forward the LLDP messages they are transparent for the partners. This causes a topology error.
In SINEMA Server unmanaged IE switches are not recognized automatically. If you use unmanaged IE switches, it might happen that when determining the topology in SINEMA Server, the topology does not recognize all the connections or possibly incorrect connections. In the processing mode, a reference topology can be configured based on the topology determined by SINEMA Server and this then represents the setpoint status of the network. This setpoint status is the basis for monitoring the network in Online mode and in view-specific topology displays. Entry 109746780 includes information about the underlying functions and setting options of SINEMA Server.

Remedy

  • The SCALANCE X-000, SCALANCE XB-000 and SCALANCE X-100, that forward LLDP messages, as well as SCALANCE X-101 media converters may not be included in the topology in the STEP 7 project. This means that you do not use the topology or you do not interconnect the unmanaged switches in the topology.
  • It is recommended to use managed IE switches for better and extended diagnostics of the network.

Note

Unmanaged IE Switches cannot be used in PROFINET networks for the function "Device replacement without exchangeable medium". Entry ID 36752540 includes a list of the devices that support "Device replacement without exchangeable medium".
Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit