AP115 UP116 Pushbutton does not work after commissioning

  • Entry
  • Associated product(s)

Problem:
AP P
ushbutton does not work after commissioning.

 

Cause:
The device does not work stable when not all group addresses of application program are linked with a group address. 

 

 

Solution:
Please connect all communication objects with group addresses. So, the device works steadily.

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit