How can a SITRANS FC430 with PROFIBUS Communication be integrated into a ABB Freelance 2000?

  • Entry
  • Associated product(s)
SITRANS FC430 PA connected to ABB Freelance 2000
 

 

The Coriolis Flowmeter SITRANS FC430 with PROFIBUS PA communication connected to ABB Freelance 2000 can only be integrated using the PROFILE GSD files. The manufacturer specific GSD file (si0181CC.gsd) is not supported by the ABB system.

Please use one of the following PROFIL GSD files:

 Registrierung notwendig  pa139700.gsd (4,6 KB)

 Registrierung notwendig  pa139701.gsd (4,7 KB)

 Registrierung notwendig  pa139702.gsd (4,8 KB)

 Registrierung notwendig  pa139742.gsd (4,9 KB)



If you have further questions, please contact our technical support.

 

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit