QUESTION:
How in the ProAgent generation run can I avoid message classes/message blocks created/renamed in STEP 7 being overwritten by the ProAgent standard message classes/message blocks?

ANSWER:
Every generation run ProAgent creates its own standard message classes/message blocks. If these message classes/message blocks have been renamed, then they are overwritten again the next generation run. This is a system property of the ProAgent Mapper.

Remedy:
To avoid this behavior you have to do a ProAgent generation run and configure your own message classes/message blocks in addition to the standard message classes/message blocks (do not rename them, but add new ones).
Then, at the next generation run, the standard message classes/message blocks are created again without overwriting the newly added message classes/message blocks.


Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit
https://www.siemens.com/cybersecurity#Ouraspiration.
Support to the statistics