AE/AR driver signals "S-321" for 6DS1730-8AA module

  • Entry
  • Associated product(s)

QUESTION:
When accessing the 6DS1730-8AA module, the AE/AR driver (or TM_AE of
PCS 7/TM-EA) signals "S-321". The electrical components of the module seem
to be OK. What shall we do?

ANSWER:
Please check whether the jumper X10/15-16 on the 6DS1730-8AA module
(marked "Reserve" in the Operating Instructions) has erroneously been installed
during commissioning (address setting). This jumper must never be installed.
It is open when the module is delivered from the factory.

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit