What does resetting the input ON on the FB37 OutputMM4_DP do to the MICROMASTER 4 connected?
-
Entry
-
Associated product(s)
Description:
The MICROMASTER provides the parameter
option for OFF1 of keeping the pulses present for a certain period
of time (P2168).
This is not possible when used with FB37 OutputMM4_DP, because
when switching off OFF1 (via the block input ON = 0 => Control
word bit 0 = 0) it also triggers the pulse inhibitor (control word
bit 3 = 0).
Notes:
- The time configured in the MICROMASTER 4 via parameter P2168 until inhibition of the inverter pulse is therefore not effective, because the pulses are already inhibited by the control word.
- Remedy: Use the FB OutputUniversal (FB 36), which specifies the speed setpoint and program the delay via the user program.
Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit
https://www.siemens.com/cybersecurity#Ouraspiration.
Also available in the following languages:
- German
- French
- Italian
- Spanish
- Chinese
Entry belongs to product tree folder(s):
- Automation Technology Industry software Automation software TIA Portal PLC programming STEP 7 (TIA Portal) Optionen Easy Motion Control
- Automation Technology Automation Systems Industrial Automation Systems SIMATIC Software for SIMATIC Controller STEP 7 V5.x Options for engineering and drive technology Easy Motion Control
Rate entry
Requests and feedback
What do you want to do?
- You have a technical question / problem: Ask the Technical Support
- You want to discuss in our forum and exchange experiences with other users
- You want to create CAx data for one or more products
- You would like to send us feedback on this Entry
Support to the statistics
With this function the IDs found are listed according to number (format .txt).
Copy URL
mySupport Cockpit
All information on Easy Motion Control
Related links