Entry type: FAQ, Entry ID: 36317, Entry date: 03/27/1996
(1)
Rate

OP3 - Transfer mode

  • Entry
  • Associated product(s)

PROBLEM:
How can you switch the OP3 into transfer mode?

ANSWER:
The OP3 always has a standard English configuration integrated in the FW. When the OP3 is first initialized, it starts up with this standard configuration.

You change to transfer mode as follows:

  1. Change to "System" image
  2. Select the mode required with SHIFT+CURSOR
  3. Enter the password "100"
  4. Select the mode required and press ENTER

If a custom configuration is loaded that does not include the standard function "Change mode", you must make a general reset by pressing the key combination"ESC+ CURSOR right + CURSOR down" and then the standard English configuration is loaded.
The power on the OP must be switched off before pressing the 3-key combination. The 3-key combination must be pressed and held when the power is switched on again on the OP.

Security information
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about industrial security, please visit