Siemens Industry Online Support
Siemens AG
Entry type: FAQ Entry ID: 39204174, Entry date: 10/30/2009
(0)
Rate

Guide values for the trip temperatures of slot thermometers

  • Entry
  • Associated product(s)

 

QUESTION:

 

 

 

 

 

Which guide values apply to the values set for temperature monitoring?


ANSWER / REMEDY / NOTES:

  

 

 

 

 

Priority must be given to the limit values specified in the machine documentation!
   

Standard set values (T = normal operating temperature):

Winding:

Warning: T + 10 K
Switch off: T + 15 K (max. 155°C)

 

Roller bearing:

Warning: T + 5 K
Switch off: T + 10 K (max. 120°C)

 

Journal bearing:

Warning: T + 2 K
Switch off: T + 5 K (max. 100°C)
     

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit