How much Hz amount the maximum pulse frequency at the Digital Inputs of SENTRON PAC3200, SENTRON PAC4200 with and without Expansion Module PAC 4DI/2DO?

  • Entry
  • Associated product(s)

QUESTION:

 

How much Hz amount the maximum pulse frequency at the Digital Inputs of SENTRON PAC3200, SENTRON PAC4200 with and without Expansion Module PAC 4DI/2DO?

ANSWER:

 

SENTRON PAC3200

Digital inputs
 

Number

1 input

Type

external power supply

Input voltage

 

for DC / rated value

DC 24V

 

for DC / maximum

DC 30V

 

final value for signal <0> - recognition

DC 8V

 

initial value for signal <1> - recognition

DC 13V

Input current

 

for signal <1>

7mA

Initial delay time

 

for signal <1> after <0> / maximum

5ms

 

for signal <0> after <1> / maximum

5ms

Pulse frequency

 

maximum pulse frequency

17Hz



SENTRON PAC4200

Digital inputs
 

Number

2 inputs

Type

external power supply

Input voltage

 

for DC / rated value

DC 24V

 

for DC / maximum

DC 30V

 

final value for signal <0> - recognition

DC 10V

 

initial value for signal <1> - recognition

DC 19V

Input current

 

for signal <1>

4mA

Initial delay time

 

for signal <1> after <0> / maximum

5ms

 

for signal <0> after <1> / maximum

5ms

Pulse frequency

 

maximum pulse frequency

20Hz


 

Expansion Module PAC 4DI/2DO

Digital inputs
 

Number

4 inputs

Type

Internal power supply or external power supply

Input voltage

 

for DC / rated value

DC 24V (optional)

 

for DC / maximum

DC 30V (optional)

Input resistance

 

for signal <1>

<= 1 kOhm

 

for signal <0>

>= 100 kOhm

Input current

 

for signal <1>

>= 2,5mA

 

for signal <0>

<= 0,5mA

Pulse frequency

 

maximum pulse frequency

20Hz


Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit