How can the energy counters of a SENTRON PAC3100 be selected via Modbus RTU as a 32bit value?

  • Entry
  • Associated product(s)

QUESTION:

How can the energy counters of a SENTRON PAC3100 be selected via Modbus RTU as a 32bit value?

ANSWER:

The energy counter of SENTRON PAC3100 are now available as a 32bit value via Modbus RTU. With the help of the function code 0x03 and 0x04, these data ca be read out from the following tabs:

 

 

Offset

Numbers of registers

Name

Format

Unit

Value range

Access

2803

2

Active energy (import, export, balance)

Float

Wh

Overflow 1.0e+12

R

2805

2

Reactive energy (import, export,

balance)

Float

varh

Overflow 1.0e+12

R


Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit