Resetting counters 1-4 on the IP242B

  • Entry
  • Associated product(s)

PROBLEM:
Why is it impossible to reset counters 1-4 on the IP242B?

ANSWER:
Counters 1-4 in the IP242B Versions 1.1 and 1.2 cannot be reset with the command "RZ” (reset counter) if counter 5 is not reset too.

Solution: Set the counters to zero with the command "LD” (load date).

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit