Entry type: Product note Entry ID: 4160735, Entry date: 08/27/1996
(0)
Rate

355 Memory Module for S5-155U Wrong Jumper Settings

  • Entry
  • Associated product(s)
                                                                            

                                                                            

Concerns the product with Order No.:                                        

                                                                            

6ES5 355-3UA11    355 memory module for S5-155U                             

                                                                            

                                                                            

                                                                            

Jumper X23 has been placed wrongly on some of the modules                   

shipped. This prevents the CPU from going into RUN condition.               

The correct jumper setting is: coding plug connected to pins                

1-2 and 3-4; pins 5-6 to remain open.                                       

                                                                            

                                                                            

                 -------------------------------                            





Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit