"SIPLUS extreme - Now even stronger!" Delivery Release for the application from -1.000 to +5.000 meters of altitude

  • Entry
  • Associated product(s)

The product line SIPLUS extreme offers from now on all components, except fail safe components, for application from -1.000 to +5.000 meters of altitude . These meets a working range of 1.080 hPa overpressure and 540 hPa low-pressure. SIPLUS extreme is the product line with refined components based on I IA/DT standard products.

 

Application area of SIPLUS extreme components:
 

environmental conditions  air pressure

1.080...795 hPa (-1.000 to +2.000m) no derating
795...658 hPa (+2.000 to +3.500m) derating 10 K of the maximum upper operating temperature
658...540 hPa (+3.500 to +5.000m) derating 20 K of the maximum upper operating temperature

For information of the SIPLUS products go to: www.siemens.com/siplus-extreme

For further questions, please contact your Siemens-branch office.

Siemens contact in the Internet

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit
https://www.siemens.com/cybersecurity#Ouraspiration.
Rate entry
no rating
Requests and feedback
What do you want to do?
Hinweis: Das Feedback bezieht sich immer auf den vorliegenden Beitrag. Ihre Nachricht wird an die Redakteure im Online Support gesendet. In einigen Tagen erhalten Sie von uns eine Antwort, wenn Ihr Feedback das erfordert. Ist für uns alles klar, werden wir Ihnen nicht mehr antworten.