IP 260 - New Product Version 2

  • Entry
  • Associated product(s)
                                                                            

                                                                            

                                                                            

Concerns products with the  Order Nos.:                                     

                                                                            

6ES5 260-4UA11  IP 260 Closed-loop Control Module                           

6ES5 848-8PR01  IP 260 Standard FBs for S5-115U/135U/150U/155U              

6ES5 895-5SE11  COM 260 System Program for S5 DOS Programmers, G            

6ES5 895-5SE21  COM 260 System Program for S5 DOS Programmers, E            

6ES5 895-5SE31  COM 260 System Program for S5 DOS Programmers, F            

                                                                            

                                                                            

The new product version 2 of the IP 260 has undergone the fol-              

lowing functional changes:                                                  

                                                                            

1. If the BASP signal (output disable) goes HIGH, the IP 260                

   no longer detects a CPU failure. This will happen only if                

   communication between CPU (via FB 170) and IP 260 has                    

   been interrupted.                                                        

   Reason for modification: In some cases, the BASP signal was              

   HIGH, but the CPU was in the RUN state.                                  

                                                                            

2. Limit switch evaluation                                                  

   It is now possible to move in the "Close" direction, even                

   if the signal to the "Open" limit switch is HIGH.                        

                                                                            

The modification is free of charge. Please contact your local               

Siemens office.                                                             





Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit