SIMODRIVE 611U: PROFIBUS changing the baud rate

  • Entry
  • Associated product(s)
QUESTION:
Is it possible to set the transmission rate (baudrate) on SIMODRIVE 611U?

ANSWER:
No, the SIMODRIVE 611U is a PROFIBUS slave and automatically set to the baudrate of the DP Master Class 1 (DPMC1).
The parameter P0963 baudrate PROFIBUS shows online the current baudrate.

The DP Master Class 2 (DPMC2) - programming unit, laptop, PC or HMI – must be set to the baudrate of DP Master Class 1 for configuring, commissioning, operating and monitoring / HMI in bus mode.
Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit