×
Siemens Industry Online Support
Siemens AG
Entry type: FAQ Entry ID: 50559894, Entry date: 03/10/2016
(0)
Rate

3NW7 - Leakage current and minimum voltage for the signal detectors

  • Entry
  • Associated product(s)
Leakage current and the minimum voltage for the signal detectors of the cylindrical fuse holder 3NW7...?

QUESTION:

How big is the leakage current and the minimum voltage for the signal detectors of the cylindrical fuse holder 3NW7...?

 

ANSWER:

The leakage current is 0,1 ... 0,2 mA at tripped fuse.

The minimum voltage is 45 V AC/DC, which the diode needs.
At 45 V AC/DC the diode begins in a small rhythm with approx. 1 Hz to blink.


Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit
https://www.siemens.com/cybersecurity#Ouraspiration.