Siemens Industry Online Support
Siemens AG
Entry type: FAQ, Entry ID: 51930734, Entry date: 08/31/2011
(0)
Rate

What must be considered when using the SIMATIC S7 FM354 module with incremental encoder?

  • Entry
  • Associated product(s)
Description
When using an incremental encoder the resolution of the encoder must not exceed 8000 steps/rotation. If the resolution is exceeded (10,000 steps/rotation, for example), then the zero mark monitoring function can no longer be executed correctly.
Security information
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about industrial security, please visit
http://www.siemens.com/industrialsecurity.