Can I get the pressure reading of the Vortex pressure sensor unit via HART?
-
Entry
-
Associated product(s)
Question:
Can I get the pressure reading of the Vortex pressure sensor unit via HART?
Answer:
Yes. Enter PDM and navigate to the operating settings - status Temp. Sensor section and then select "enabled".
The pressure readouts are now accessible in the HART section (pressure output in section SV or QV).
- Remember to upload the change status to the unit.
- Ensure the Vortex flowmeter is operating using firmware 1.3 (it is displayed when starting up the unit).
Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit