Confirmation: Equality of structure MCCB 3VL25*/3VL35*

  • Entry
  • Associated product(s)

The enclosed document confirms that the structure of MCCB 3VL25* and 3VL35* is equal to the structure of the old MCCB 3VL21*/3VL31*.

Productdescription:
The enclosed document confirms that: - 3VL25* are identical in construction to 3VL21* - 3VL35* are identical in construction to 3VL31* - electrical data of 3VL25*/3VL35* have been changed as follows: * 3VL25*/3VL35* circuit breakers are not suitable for 600V networks (Delta) * 3VL25*/3VL35* circuit breakers are suitable for 600/347V (Wye) but have a reduced switching capability of 18 kA for all three switching capacity classes N, H and L compared to the precursor 3VL21*/3VL31*

Target market:
worldwide
Link:
 
 
 Bescheinigung_Baugleichheit-Confirmation_equality_of_structure_3VL25-3VL35.pdf ( 76 KB )
Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit