SINAMICS G: Speed Control of a G110M / G120 (Startdrive) with S7-1500 (TO) via PROFINET or PROFIBUS with Safety Integrated (via Terminal) and HMI
-
Entry
-
Associated product(s)
Task
SIMATIC S7-1500 CPUs support the connection of PROFIdrive-capable drives via PROFINET or PROFIBUS as a speed axis or positioning axis.
The standardized PLCopen blocks make configuration particularly easy.
Solution
This application example shows how to configure and commission the SINAMICS G120 and the SIMATIC S7-1500 using the technological functions of the SIMATIC S7-1500.
The application example does not include a reusable block. Instead, it provides a project that allows the user to conveniently familiarize with the properties of the motion control instructions (PCLopen blocks) and test them via HMI.
Downloads
The following example projects where designed with these versions:
- STEP 7 Professional V13 SP1 Update9
- WinCC advanced V13 SP1 Update9
- Startdrive V13 SP1 Update3
- SINAMICS G110M/G120/G120C/G120D/G120P with FW V4.7
- S7-1500 CPU with FW 1.8 with
Technology objekt speed axis V2.0
![]()
SINAMICS G110M PN (6,5 MB)
![]()
SINAMICS G110M DP (6,9 MB)
![]()
SINAMICS G120 with CU240B-2 DP (6,9 MB)
![]()
SINAMICS G120 with CU240E-2 PN (6,5 MB)
![]()
SINAMICS G120 with CU240E-2 DP (6,9 MB)
![]()
SINAMICS G120 with CU240E-2 PN F (6,5 MB)
![]()
SINAMICS G120 with CU240E-2 DP F (6,9 MB)
![]()
SINAMICS G120 with CU250S-2 PN (6,5 MB)
![]()
SINAMICS G120 with CU250S-2 DP (6,9 MB)
![]()
SINAMICS G120C PN (6,5 MB)
![]()
SINAMICS G120C DP (6,9 MB)
![]()
SINAMICS G120D with CU240D-2 PN (6,5 MB)
![]()
SINAMICS G120D with CU240D-2 DP (6,9 MB)
![]()
SINAMICS G120D with CU240D-2 PN F (6,5 MB)
![]()
SINAMICS G120D with CU240D-2 DP F (6,9 MB)
![]()
SINAMICS G120P with CU230P-2 PN (6,5 MB)
![]()
SINAMICS G120P with CU230P-2 DP (6,9 MB)
The following example projects where designed with these versions:
- STEP 7 Professional V14
- WinCC advanced V14
- Startdrive V14
- SINAMICS G110M/G120/G120C/G120D/G120P with FW V4.7
- S7-1500 CPU with FW 1.8 with Technology objekt speed axis V2.0
![]()
SINAMICS G110M PN (6,0 MB)
![]()
SINAMICS G110M DP (7,1 MB)
![]()
SINAMICS G120 with CU240B-2 DP (7,1 MB)
![]()
SINAMICS G120 with CU240E-2 PN (6,0 MB)
![]()
SINAMICS G120 with CU240E-2 DP (7,1 MB)
![]()
SINAMICS G120 with CU240E-2 PN F (5,9 MB)
![]()
SINAMICS G120 with CU240E-2 DP F (6,8 MB)
![]()
SINAMICS G120 with CU250S-2 PN (5,9 MB)
![]()
SINAMICS G120 with CU250S-2 DP (6,8 MB)
![]()
SINAMICS G120C PN (6,0 MB)
![]()
SINAMICS G120C DP (7,1 MB)
![]()
SINAMICS G120D with CU240D-2 PN (6,0 MB)
![]()
SINAMICS G120D with CU240D-2 DP (7,1 MB)
![]()
SINAMICS G120D with CU240D-2 PN F (5,8 MB)
![]()
SINAMICS G120D with CU240D-2 DP F (7,0 MB)
![]()
SINAMICS G120P with CU230P-2 PN (5,8 MB)
![]()
SINAMICS G120P with CU230P-2 DP (7,0 MB)
The following example projects where designed with these versions:
- STEP 7 Professional V15 Update1
- WinCC advanced V15 Update1
- Startdrive V15 Update2
- SINAMICS G110M/G120/G120C/G120D/G120P with FW V4.7
- S7-1500 CPU with FW 1.8 with Technology objekt speed axis V2.0
![]()
SINAMICS G110M PN (845,5 KB)
![]()
SINAMICS G110M DP (841,9 KB)
![]()
SINAMICS G120 with CU240B-2 DP (841,7 KB)
![]()
SINAMICS G120 with CU240E-2 PN (845,1 KB)
![]()
SINAMICS G120 with CU240E-2 DP (841,8 KB)
![]()
SINAMICS G120 with CU250S-2 PN (844,7 KB)
![]()
SINAMICS G120 with CU250S-2 DP (841,7 KB)
![]()
SINAMICS G120C PN (844,8 KB)
![]()
SINAMICS G120C DP (841,6 KB)
![]()
SINAMICS G120D with CU240D-2 PN (844,8 KB)
![]()
SINAMICS G120D with CU240D-2 DP (842,0 KB)
![]()
SINAMICS G120P with CU230P-2 PN (844,7 KB)
![]()
SINAMICS G120P with CU230P-2 DP (842,0 KB)
Last Changes
Update with TIA Portal V15
Additional Keywords
motioncontrol_apc_applications
- German
Entry belongs to product tree folder(s):
- Drive Technology Converters Low voltage converters Dezentrale Frequenzumrichter SINAMICS G110M Motor-Integrated Frequency Converters
- Drive Technology Converters Low voltage converters Industry-specific frequency converters SINAMICS G120P for Pumps, Fans and Compressors SINAMICS G120P Built-In and Wall-Mounting Units
- Drive Technology Converters Low voltage converters Dezentrale Frequenzumrichter SINAMICS G120D Distributed Converters
- Drive Technology Converters Low voltage converters Standard Performance Frequency Converter SINAMICS G120 Built-In Units Control Units
- Automation Technology Automation Systems Industrial Automation Systems SIMATIC PLC Advanced Controller S7-1500 CPUs Standard-CPUs
- Automation Technology Automation Systems Industrial Automation Systems SIMATIC PLC Advanced Controller S7-1500 CPUs Failsafe CPUs
- Automation Technology Products for specific requirements Automatision technology for extreme conditions SIPLUS extreme Industrial Automation Systems Controllers SIPLUS Advanced Controller SIPLUS S7-1500 SIPLUS Central Processing Units SIPLUS Standard CPUs
- Safety systems - Safety Integrated Safety Technology for Factory Automation Drive technology SINAMICS G120 Built-in Units
- Safety systems - Safety Integrated Safety Technology for Factory Automation Drive technology SINAMICS G120D Distributed Frequency Inverters
- Automation Technology Automation Systems Industrial Automation Systems SIMATIC PLC Advanced Controller S7-1500 CPUs Compact CPUs
- You have a technical question / problem: Ask the Technical Support
- You want to discuss in our forum and exchange experiences with other users
- You want to create CAx data for one or more products
- You would like to send us feedback on this Entry