×
Siemens Industry Online Support
Siemens AG
Entry type: Download Entry ID: 79207181, Entry date: 04/05/2019
(5)
Rate

Firmware for Uninterruptable Power Supply SITOP UPS1600

  • Entry
  • Associated product(s)
Keep your uninterruptable power supply UPS1600 updated with the Firmware Update.

       

Firmware update V2.2.3

The latest firmware V2.2.3 is released for the following units of uninterruptable power supply UPS1600 and download is available for free:

  • SITOP UPS1600 10 A and 20 A with USB or PROFINET interface from Product State "6"
  • SITOP UPS1600 40 A with USB or PROFINET interface from Product State "3"

The Firmware V2.2.3 contains the rectification ofSSA-293562: Vulnerabilities in Industrial Productsand function extensions.
After consumption of stock mentioned units will be delivered with new firmware.


Function extensions

  • Support for the new engineering and monitorin software SITOP Manager
  • The uninterruptable power supply SITOP UPS1600 with PROFINET interface get an OPC UA server with this firmware update V2.2.3
  • Hysteresis for charge current management has been implemented.

Please note:

  • For an update of firmware version V2.1.x to V2.2.3 the Webserver or the SITOP UPS Manager from version 4.72.2 must be used (entry ID 75854607)!
  • For update UPS1600 with USB interface (6EP413x-3AB00-1AY0) SITOP Manager V1.0.1 (entry ID 109760607) must be used! 


Firmware update V2.0.5


The firmware V2.0.5 is released for the following units of uninterruptable power supply UPS1600 and download is available for free:

  • SITOP UPS1600 10 A and 20 A with USB or PROFINET interface from Product State "1" up to (incl.) Product State "5"
  • SITOP UPS1600 40 A with USB or PROFINET interface from Product State "1" up to (incl.) Product State "2"

Function extensions

  • The Firmware V2.2.0 contains the rectification ofSSA-293562: Vulnerabilities in Industrial Productsand function extensions.

  • Correction of the SITOP UPS1600 with firmware V2.0.4 alarm signalling (battery test alarm removed)

  • Functional scope like V2.0.4 (see below)

 

Do you know the current firmware release of your SITOP UPS1600?
  Instruction (173,0 KB) to determine the firmware release of a SITOP UPS1600


Procedure

  1. Depending on your hardware and product state please use the relevant update.
  2. Save the .zip file and unpack it to a local directory.
  3. Open the local directory and follow the instructions in the Readme *.pdf.
  4. The firmware contains third-party software components. Please observe the license provisions in file „LicenseInformation.pdf“ or "ReadMe_OSS.html".


 WARNING: During the firmware update the SITOP UPS1600 is reset. For safety reasons the output is shut off. Please make sure that the installation is not damaged by this and the PG/PC has a power supply independent of the UPS.  

 

 

Downloads:

 

10 A versions 

USB: 6EP4134-3AB0-1AY0

PROFINET: 6EP4134-3AB0-2AY0 

20 A versions

 

USB: 6EP4136-3AB0-1AY0

PROFINET: 6EP4136-3AB0-2AY0 

40 A versions


USB: 6EP4137-3AB0-1AY0

PROFINET: 6EP4137-3AB0-2AY0 

V2.2.3 Registrierung notwendig  UPDATE_SITOP-UPS1600-10A_V2-2-3.zip (8,3 MB)
 Registrierung notwendig  UPDATE_SITOP-UPS1600-20A_V2-2-3.zip (8,3 MB)
 Registrierung notwendig  UPDATE_SITOP-UPS1600-40A_V2-2-3.zip (8,3 MB)
V2.0.5 Registrierung notwendig  UPDATE_SITOP-UPS1600-10A_V2-0-5-0.zip (1,9 MB) Registrierung notwendig  UPDATE_SITOP-UPS1600-20A_V2-0-5-0.zip (1,9 MB)  Registrierung notwendig  UPDATE_SITOP-UPS1600-40A_V2-0-5-0.zip (1,9 MB)

 

Further information
SITOP in Internet at: www.siemens.com/sitop
Operating manuals(PDF) in German, English and Chinese



-------------------------------------------------------------------------------------------------------------------------------------

Previous firmware updates for uninterruptable power supply UPS1600 are available:


Firmware update V2.2.0 

The firmware V2.2.0 is released for the following units of uninterruptable power supply UPS1600 and download is available for free:

  • SITOP UPS1600 10 A and 20 A with USB or PROFINET interface from Product State "6"
  • SITOP UPS1600 40 A with USB or PROFINET interface from Product State "3"

The Firmware V2.2.0 contains the rectification ofSSA-293562: Vulnerabilities in Industrial Productsand function extensions.
After consumption of stock mentioned units will be delivered with new firmware.

Function extensions

  • The uninterruptable power supply SITOP UPS1600 with PROFINET interface get an OPC UA server with this firmware update V2.2.0.

Please note:
For an update of firmware version V2.1.x to V2.2.0 the Webserver or the SITOP UPS Manager from version 4.72.2 must be used (entry ID 75854607)!

Firmware update V2.1.2


The firmware V2.1.2 is released for the following units of uninterruptable power supply UPS1600 and download is available for free:

  • SITOP UPS1600 10 A and 20 A with USB or PROFINET interface with Product State "6"
  • SITOP UPS1600 40 A with USB or PROFINET interface with Product State "3"

Content

  • Correction of faulty signaling behavior of SITOP UPS1600 with Firmware V2.1.0
  • Functional scope like V2.1.0 and V2.0.4 (see below)

Firmware V2.1.0


The firmware V2.1.0 is released for the following units of uninterruptable power supply UPS1600:

  • SITOP UPS1600 10 A and 20 A with Product State "6"

  • SITOP UPS1600 40 A with Product State "3"

Function extensions

  • Operating SITOP UPS1600 with new battery module SITOP UPS1100 5 Ah with lithium iron phosphate storage technology (LiFePo)

Firmware update V2.0.5


The firmware V2.0.5 is released for the following units of uninterruptable power supply UPS1600 and download is available for free:

  • SITOP UPS1600 10 A and 20 A with USB or PROFINET interface up to (incl.) Product State "5"
  • SITOP UPS1600 40 A with USB or PROFINET interface up to (incl.) Product State "2"

Funtcion extensions

  • The Firmware V2.2.0 contains the rectification ofSSA-293562: Vulnerabilities in Industrial Products and function extensions.

  • Correction of the SITOP UPS1600 with firmware V2.0.4 alarm signalling (battery test alarm removed)

  • Functional scope like V2.0.4 (see below)

Firmware update V2.0.4

The firmware V2.0.4 is released for the following units of uninterruptable power supply UPS1600 and download is available for free:
  • SITOP UPS1600 10 A and 20 A with USB or PROFINET interface up to Product State "5"

  • SITOP UPS1600 40 A with USB or PROFINET interface up to Product State "2"

Function extensions

  • SITOP UPS1600 operates with new battery modules SITOP UPS1100 2.5 Ah or SITOP UPS1100 12 Ah.
  • You use the SITOP UPS Manager and want to connect several slaves.
  • You want to buffer a PC with installed SoftPLC and PN interface with the SITOP UPS1600. 


Please note:
For an update of firmware version V2.1.x to V2.2.0 the SITOP UPS Manager from version 4.72.2 must be used (entry ID 75854607)!

 

Do you know the current firmware release of your SITOP UPS1600?
  Instruction (173,0 KB) to determine the firmware release of a SITOP UPS1600


Procedure

  1. Depending on your hardware and product state please use the relevant update.
  2. Save the .zip file and unpack it to a local directory.
  3. Open the local directory and follow the instructions in the Readme *.pdf.
  4. The firmware contains third-party software components. Please observe the license provisions in file „LicenseInformation.pdf“ or "ReadMe_OSS.html".



 WARNING: During the firmware update the SITOP UPS1600 is reset. For safety reasons the output is shut off. Please make sure that the installation is not damaged by this and the PG/PC has a power supply independent of the UPS.  

 

Download

 10 A versions 

USB: 
6EP4134-3AB0-1AY0 
PROFINET: 6EP4134-3AB0-2AY0 

20 A versions 


USB: 
6EP4136-3AB0-1AY0 
PROFINET: 6EP4136-3AB0-2AY0 
40 A versions 

USB: 
6EP4137-3AB0-1AY0 
PROFINET: 6EP4137-3AB0-2AY0 
 V2.2.0  Registrierung notwendig  UPDATE_SITOP-UPS1600-10A_V2-2-0.zip (7,8 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-20A_V2-2-0.zip (7,8 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-40A_V2-2-0.zip (7,8 MB) 
 V2.1.2 Registrierung notwendig  UPDATE_SITOP-UPS1600-10A_V2-1-2.zip (4,9 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-20A_V2-1-2.zip (4,9 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-40A_V2-1-2.zip (4,9 MB) 
 V2.0.5  Registrierung notwendig  UPDATE_SITOP-UPS1600-10A_V2-0-5-0.zip (1,9 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-20A_V2-0-5-0.zip (1,9 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-40A_V2-0-5-0.zip (1,9 MB) 
 V2.0.4  Registrierung notwendig  UPDATE_SITOP-UPS1600-10A_V2.0.4.zip (1,9 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-20A_V2.0.4.zip (1,9 MB)   Registrierung notwendig  UPDATE_SITOP-UPS1600-40A_V2.0.4.zip (1,9 MB) 
 V1.22  Registrierung notwendig  en_firmwareupdate_v122_6ep4134.zip (1,4 MB)   Registrierung notwendig  en_firmwareupdate_v122_6ep4136.zip (1,4 MB)  ---

 

 

Further information

SITOP in Internet at: www.siemens.com/sitop
Operating manuals(PDF) in German, English and Chinese


Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit
https://www.siemens.com/cybersecurity#Ouraspiration.