How can you use the PID Self-Tuner V5 for negative control direction (e.g. for cooling control)?

  • Entry
  • Associated product(s)

Instructions:
The PID Self-Tuner cannot calculate a negative amplification factor and always requires a positive change of setpoint value.

Remedy:
To accomplish a negative control direction you must make the following changes in the "Controller/Tuner" interconnection:

  1. Negate the setpoint value ("SP") to the self-tuner (multiply by -1.0) and likewise the output value "SP_OUT" from the self-tuner to the controller.
  2. Negate the actual controller value from the controller to the self-tuner ("PV").
  3. Negate the amplification factor "GAIN" to the controller.

Keywords:
Self-tuner programming

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit