What should you watch out for when installing, licensing and configuring SIMATIC powerrate in the server/client mode?

  • Entry
  • Associated product(s)

Description
Below we provide you with important information about installing, licensing and configuring SIMATIC powerrate in the server/client mode.

  • Installation
    You must install SIMATIC powerrate on the following stations:
    - Engineering Station
    - OS Server (on both servers in the case of redundancy)
    - OS Clients
    Note
    A valid version of EXCEL must be already installed for the installation of the Reporting component of SIMATIC powerrate.
  • Licensing
    You must install a SIMATIC powerrate license on the following stations:
    - OS Single Station
    - OS Server (on both servers in the case of redundancy)
  • Configuration
    You must pay attention to the following settings with SIMATIC powerrate in server/client mode:
    - On all clients you must set a standard server for the User Archive to be able to store the configuration of the load management.
    - On all clients you must set a standard server for Alarm Logging to be able to generate operator inputs.

Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit