SIMATIC S7-300 S7-300 Module data

Document: S7-300 Module data (06/2017, English)
Type of topic: Fact

Representation of the values for analog input channels

Measured value resolution

The resolution of the analog values may differ, based on the analog module and module parameters. At resolutions < 15 bits, all bits identified by "x" are set to "0".


Note

This resolution does not apply to temperature values. Converted temperature values are the result of a conversion in the analog module.



Table: Supported analog value resolutions

Resolution

in bits (+ sign)

Units

Analog value

 

dec

hex

high byte

low byte

8

128

80H

Sign 0 0 0 0 0 0 0

1 x x x x x x x

9

64

40H

Sign 0 0 0 0 0 0 0

0 1 x x x x x x

10

32

20H

Sign 0 0 0 0 0 0 0

0 0 1 x x x x x

11

16

10H

Sign 0 0 0 0 0 0 0

0 0 0 1 x x x x

12

8

8H

Sign 0 0 0 0 0 0 0

0 0 0 0 1 x x x

13

4

4H

Sign 0 0 0 0 0 0 0

0 0 0 0 0 1 x x

14

2

2H

Sign 0 0 0 0 0 0 0

0 0 0 0 0 0 1 x

15

1

1H

Sign 0 0 0 0 0 0 0

0 0 0 0 0 0 0 1

Binary representation of input ranges

Table: Bipolar input ranges

Units

Measured value in %

Data word

Range

 

 

215

214

213

212

211

210

29

28

27

26

25

24

23

22

21

20

 

32767

>118.515

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Overflow

32511

117.589

0

1

1

1

1

1

1

0

1

1

1

1

1

1

1

1

Overshoot range

27649

>100.004

0

1

1

0

1

1

0

0

0

0

0

0

0

0

0

1

27648

100.000

0

1

1

0

1

1

0

0

0

0

0

0

0

0

0

0

Rated range

1

0.003617

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0.000

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

-1

-0.003617

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

-27648

-100.000

1

0

0

1

0

1

0

0

0

0

0

0

0

0

0

0

-27649

≤-100.004

1

0

0

1

0

0

1

1

1

1

1

1

1

1

1

1

Undershoot range

-32512

-117.593

1

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

-32768

≤-117.596

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Underflow

Table: Unipolar input ranges

Units

Measured value in %

Data word

Range

 

 

215

214

213

212

211

210

29

28

27

26

25

24

23

22

21

20

 

32767

≥118.515

0

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Overflow

32511

117.589

0

1

1

1

1

1

1

0

1

1

1

1

1

1

1

1

Overshoot

range

range

27649

≥100.004

0

1

1

0

1

1

0

0

0

0

0

0

0

0

0

1

27648

100.000

0

1

1

0

1

1

0

0

0

0

0

0

0

0

0

0

1

0.003617

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

Rated range

0

0.000

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

-1

-0.003617

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Undershoot

range

range

-4864

-17.593

1

1

1

0

1

1

0

1

0

0

0

0

0

0

0

0

-32768

≤-17.596

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Underflow

Representation of analog values in voltage measuring ranges

Table: Representation of analog values in the ±1 V to ±10 V voltage measuring range Representation of analog valuesFor voltage measuring ranges

System

Voltage measuring range

 

dec

hex

±10 V

±5 V

±2.5 V

±1 V

 

32767

7FFF

11.851 V

5.926 V

2.963 V

1.185 V

Overflow

32512

7F00

 

 

 

 

32511

7EFF

11.759 V

5.879 V

2.940 V

1.176 V

Overshoot range

27649

6C01

 

 

 

 

27648

6C00

10 V

5 V

2.5 V

1 V

Rated range

20736

5100

7.5 V

3.75 V

1.875 V

0.75 V

1

1

361.7 µV

180.8 µV

90.4 µV

36.17 µV

0

0

0 V

0 V

0 V

0 V

-1

FFFF

 

 

 

 

-20736

AF00

-7.5 V

-3.75 V

-1.875 V

-0.75 V

-27648

9400

-10 V

-5 V

-2.5 V

-1 V

-27649

93FF

 

 

 

 

Undershoot range

-32512

8100

-11.759 V

-5.879 V

-2.940 V

-1.176 V

-32513

80FF

 

 

 

 

Underflow

-32768

8000

-11.851 V

-5.926 V

-2.963 V

-1.185 V

Table: Representation of analog values in the ±80 mV to ±500 mV voltage measuring ranges Representation of analog valuesFor voltage measuring ranges

System

Voltage measuring range

dec

hex

±500 mV

±250 mV

±80 mV

 

32767

7FFF

592.6 mV

296.3 mV

94.8 mV

Overflow

32512

7F00

 

 

 

32511

7EFF

587.9 mV

294.0 mV

94.1 mV

Overshoot range

27649

6C01

 

 

 

27648

6C00

500 mV

250 mV

80 mV

Rated range

20736

5100

375 mV

187.5 mV

60 mV

1

1

18.08 µV

9.04 µV

2.89 µV

0

0

0 mV

0 mV

0 mV

-1

FFFF

 

 

 

-20736

AF00

-375 mV

-187.5 mV

-60 mV

-27648

9400

-500 mV

-250 mV

-80 mV

-27649

93FF

 

 

 

Undershoot range

-32512

8100

-587.9 mV

-294.0 mV

-94.1 mV

-32513

80FF

 

 

 

Underflow

-32768

8000

-592.6 mV

-296.3 mV

-94.8 mV

Table: Representation of analog values in the 1 V to 5 V and 0 V to 10 V voltage measuring ranges Representation of analog valuesFor voltage measuring ranges

System

Voltage measuring range

dec

hex

1 V to 5 V

0 V to 10 V

 

32767

7FFF

5.741 V

11.852 V

Overflow

32512

7F00

 

 

32511

7EFF

5.704 V

11.759 V

Overshoot range

27649

6C01

 

 

27648

6C00

5 V

10 V

Rated range

20736

5100

4 V

7.5 V

1

1

1 V + 144.7 µV

0 V + 361.7 µV

0

0

1 V

0 V

-1

FFFF

 

Negative values are not supported

Undershoot range

-4864

ED00

0.296 V

-4865

ECFF

 

Underflow

-32768

8000

 

Representation of analog values in the current measuring ranges

Table: Representation of analog values in the ±3.2 mA to ±20 mA current measuring ranges Representation of analog valuesFor current measuring ranges

System

Current measuring range

dec

hex

±20 mA

±10 mA

±3.2 mA

 

32767

7FFF

23.70 mA

11.85 mA

3.79 mA

Overflow

32512

7F00

 

 

 

 

32511

7EFF

23.52 mA

11.76 mA

3.76 mA

Overshoot range

27649

6C01

 

 

 

27648

6C00

20 mA

10 mA

3.2 mA

Rated range

20736

5100

15 mA

7.5 mA

2.4 mA

1

1

723.4 nA

361.7 nA

115.7 nA

0

0

0 mA

0 mA

0 mA

-1

FFFF

 

 

 

-20736

AF00

-15 mA

-7.5 mA

-2.4 mA

-27648

9400

-20 mA

-10 mA

-3.2 mA

-27649

93FF

 

 

 

Undershoot range

-32512

8100

-23.52 mA

-11.76 mA

-3.76 mA

-32513

80FF

 

 

 

Underflow

-32768

8000

-23.70 mA

-11.85 mA

-3.79 mA

Table: Representation of analog values in the 0 mA to 20 mA and 4 mA to 20 mA current measuring ranges Representation of analog valuesFor current measuring ranges

System

Current measuring range

dec

hex

0 mA to 20 mA

4 mA to 20 mA

 

32767

7FFF

23.70 mA

22.96 mA

Overflow

32512

7F00

 

 

32511

7EFF

23.52 mA

22.81 mA

Overshoot range

27649

6C01

 

 

27648

6C00

20 mA

20 mA

Rated range

20736

5100

15 mA

16 mA

1

1

723.4 nA

4 mA + 578.7 nA

0

0

0 mA

4 mA

-1

FFFF

 

 

Undershoot range

-4864

ED00

-3.52 mA

1.185 mA

-4865

ECFF

 

 

Underflow

-32768

8000

 

 

Representation of the analog values of resistive transducers

Table: Representation of the analog values of 6 kΩ; 10 kΩ and from 150 Ω to 600 Ω resistive transducers Representation of analog valuesof resistive transducers

System

Resistive transducer range

dec

hex

6kΩ

10 kΩ

150 Ω

300 Ω

600 Ω

 

32767

7FFF

7.111 kΩ

11.852 kΩ

177.77 Ω

355.54 Ω

711.09 Ω

Overflow

32512

7F00

 

 

176.39 Ω

352.78 Ω

705.55 Ω

32511

7EFF

7.055 kΩ

11.759 kΩ

176.38 Ω

352.77 Ω

705.53 Ω

Overshoot range

27649

6C01

 

 

 

 

 

27648

6C00

6.0 kΩ

10 kΩ

150 Ω

300 Ω

600 Ω

Rated range

20736

5100

4.5 kΩ

7.5 kΩ

112.5 Ω

225 Ω

450 Ω

1

1

217.0 mΩ

361.7 mΩ

5.43 mΩ

10.85 mΩ

21.70 mΩ

0

0

0 Ω

0 Ω

0 Ω

0 Ω

0 Ω

 

 

(negative values are physically impossible)

Undershoot range

Representation of analog values for resistance thermometers Pt x00 and Pt x00 GOST (0.003850) standard

Table: Representation of analog values for resistance thermometers PT 100, 200, 500,1000 and PT 10, 50,100, 500 GOST (0.003850) standard Representation of analog valuesfor resistance thermometers

Pt x00 Standard / GOST in °C (1 digit = 0.1°C)

Units

Pt x00 Standard/ GOST in °F (1 digit = 0.1 °F)

Units

Pt x00 Standard/ GOST in K (1 digit = 0.1 K)

Units

Range

dec

hex

dec

hex

dec

hex

> 1000.0

32767

7FFFH

> 1832.0

32767

7FFFH

> 1273.2

32767

7FFFH

Overflow

1000.0

:

850.1

10000

:

8501

2710H

:

2135H

1832.0

:

1562.1

18320

:

15621

4790H

:

3D05H

1273.2

:

1123.3

12732

:

11233

31BCH

:

2BE1H

Overshoot range

850.0

:

-200.0

8500

:

-2000

2134H

:

F830H

1562.0

:

-328.0

15620

:

-3280

3D04H

:

F330H

1123.2

:

73.2

11232

:

732

2BE0H

:

2DCH

Rated range

-200.1

:

-243.0

-2001

:

-2430

F82FH

:

F682H

-328.1

:

-405.4

-3281

:

-4054

F32FH

:

F02AH

73.1

:

30.2

731

:

302

2DBH

:

12EH

Undershoot range

< - 243.0

-32768

8000H

< - 405.4

-32768

8000H

<  30.2

32768

8000H

Underflow

Representation of the analog values of Pt x00 GOST (0.003910) standard resistance thermometers

Table: Representation of the analog values of Pt 10, 50, 100, 500 GOST (0.003910) standard resistance thermometers Representation of analog valuesfor resistance thermometers

Pt x00 GOST Standard in °C (1 digit = 0.1°C)

Units

Pt x00 GOST Standard in °F (1 digit = 0.1 °F)

Units

Range

dec

hex

dec

hex

> 1295.0

32767

7FFFH

> 2363.0

32767

7FFFH

Overflow

1295.0

:

1100.1

12950

:

11001

3296H

:

2AF9H

2363.0

:

2012.1

23630

:

20121

5CE4H

:

4E99H

Overshoot range

1100.0

:

-260.0

11000

:

-2600

2AF8H

:

F5D8H

2012.0

:

-436.0

20120

:

-4360

4E98H

:

EEF8H

Rated range

-260.1

:

-273.2

-2601

:

-2732

F5D7H

:

F554H

-436.1

:

-459.7

-4361

:

-4597

EEF7H

:

EE0BH

Undershoot range

< - 273.2

-32768

8000H

< - 459.7

-32768

8000H

Underflow

Representation of analog values for Pt x00 and Pt x0 GOST (0.003850 and 0.003910) climatic resistance thermometers

Table: Representation of analog values for Pt 100, 200, 500,1000 and Pt 10, 50, 100, 500 GOST (0.003850 and 0.003910) climatic resistance thermometers Representation of analog valuesfor resistance thermometers

Pt x00 climatic/GOST in °C (1 digit = 0.01 °C)

Units

Pt x00 climatic/GOST in °F (1 digit = 0.01 °F)

Units

Range

dec

hex

dec

hex

> 155.00

32767

7FFFH

> 311.00

32767

7FFFH

Overflow

155.00

:

130.01

15500

:

13001

3C8CH

:

32C9H

311.00

:

266.01

31100

:

26601

797CH

:

67E9H

Overshoot range

130.00

:

-120.00

13000

:

-12000

32C8H

:

D120H

266.00

:

-184.00

26600

:

-18400

67E8H

:

B820H

Rated range

-120.01

:

-145.00

-12001

:

-14500

D11FH

:

C75CH

-184.01

:

-229.00

-18401

:

-22900

B81FH

:

A68CH

Undershoot range

< - 145.00

-32768

8000H

< - 229.00

-32768

8000H

Underflow

Representation of the analog values of Ni x00 Standard resistance thermometers

Table: Representation of the analog values of Ni100, 120, 200, 500, 1000 and LG-Ni 1000 resistance thermometers Representation of analog valuesfor resistance thermometers

Ni x00 Standard in °C (1 digit = 0.1°C)

Units

Ni x00 Standard in °F (1 digit = 0.1 °F)

Units

Ni x00 standard in K (1 digit = 0.1 K)

Units

Range

dec

hex

dec

hex

dec

hex

> 295.0

32767

7FFFH

> 563.0

32767

7FFFH

> 568.2

32767

7FFFH

Overflow

295.0

:

250.1

2950

:

2501

B86H

:

9C5H

563.0

:

482.1

5630

:

4821

15FEH

:

12D5H

568.2

:

523.3

5682

:

5233

1632H

:

1471H

Overshoot range

250.0

:

-60.0

2500

:

-600

9C4H

:

FDA8H

482.0

:

-76.0

4820

:

-760

12D4H

:

FD08H

523.2

:

213.2

5232

:

2132

1470H

:

854H

Rated range

 -60.1

:

-105.0

-601

:

-1050

FDA7H

:

FBE6H

 -76.1

:

-157.0

-761

:

-1570

FD07H

:

F9DEH

 213.1

:

168.2

2131

:

1682

853H

:

692H

Undershoot range

 < -105.0

-32768

8000H

< -157.0

-32768

8000H

 < 168.2

32768

8000H

Underflow

Representation of the analog values of Ni x00 climate resistance thermometers

The following table shows the analog values for the resistance thermometer Nix00 Climatic for all analog input modules.

Exceptions:

  • Analog input module AI 8x12-bit; 6ES7331-7KF02-0AB0
  • Analog input module AI 2x12-bit; 6ES7331-7KB02-0AB0

There is no overrange for these analog input modules. Overflow begins at 240 °C and is encoded with 7FFFH.

Table: Representation of the analog values of Ni 100, 120, 200, 500, 1000 and LG-Ni 1000 resistance thermometers Representation of analog valuesfor resistance thermometers

Ni x00 climatic in °C (1 digit = 0.01 °C)

Units

Ni x00 climatic in °F (1 digit = 0.01 °F)

Units

Range

dec

hex

dec

hex

> 295.00

32767

7FFFH

> 327.66

32767

7FFFH

Overflow

295.00

:

250.01

29500

:

25001

733CH

:

61A9H

327.66

:

280.01

32766

:

28001

7FFEH

:

6D61H

Overshoot range

250.00

:

-60.00

25000

:

-6000

61A8H

:

E890H

280.00

:

-76.00

28000

:

-7600

6D60H

:

E250H

Rated range

-60.01

:

-105.00

-6001

:

-10500

E88FH

:

D6FCH

-76.01

:

-157.00

-7601

:

-15700

E24FH

:

C2ACH

Undershoot range

< - 105.00

-32768

8000H

< - 157.00

-32768

8000H

Underflow

Representation of the analog values of Ni 100 GOST Standard resistance thermometers

Table: Representation of the analog values of Ni 100 GOST Standard resistance thermometers Representation of analog valuesfor resistance thermometers

Ni 100 GOST Standard in °C (1 digit = 0.1°C)

Units

Ni 100 GOST Standard in °F (1 digit = 0.1 °F)

Units

Range

dec

hex

dec

hex

> 212.4

32767

7FFFH

> 414.3

32767

7FFFH

Overflow

212.4

:

180.1

2124

:

1801

084CH

:

0709H

414.3

:

356.1

4143

:

3561

102FH

:

0DE9H

Overshoot range

180.0

:

-60.0

1800

:

-600

0708H

:

FDA8H

356.0

:

-76.0

3560

:

-760

0DE8H

:

FD08H

Rated range

-60.1

:

-105.0

-601

:

-1050

FDA7H

:

FBE6H

-76.1

:

-157.0

-761

:

-1570

FD07H

:

F9DEH

Undershoot range

< - 105.0

-32768

8000H

< - 157.0

-32768

8000H

Underflow

Representation of the analog values of Ni 100 GOST Klima resistance thermometers

Table: Representation of the analog values of Ni 100 GOST Klima resistance thermometers Representation of analog valuesfor resistance thermometers

Ni 100 GOST Klima in °C (1 digit = 0.1°C)

Units

Ni 100 GOST Klima in °F (1 digit = 0.1 °F)

Units

Range

dec

hex

dec

hex

> 212.40

32767

7FFFH

> 327.66

32767

7FFFH

Overflow

212.40

:

180.01

21240

:

18001

52F8H

:

4651H

327.66

:

280.01

32766

:

28001

7FFEH

:

6D61H

Overshoot range

180.00

:

-60.00

18000

:

-6000

4650H

:

E890H

280.00

:

-76.00

28000

:

-7600

6D60H

:

E250H

Rated range

-60.01

:

-105.00

-6001

:

-10500

E88FH

:

D6FCH

-76.01

:

-157.00

-7601

:

-15700

E24FH

:

C2ACH

Undershoot range

< - 105.00

-32768

8000H

< - 157.00

-32768

8000H

Underflow

Representation of the analog values for Cu 10 standard resistance thermometers

Table: Representation of the analog values for Cu 10 standard resistance thermometers Representation of analog valuesfor resistance thermometers

Cu 10 standard in °C (1 digit = 0.01 °C)

Units

Cu 10 standard in °F (1 digit = 0.01 °F)

Units

Cu 10 standard in K (1 digit = 0.01 K)

Units

Range

dec

hex

dec

hex

dec

hex

> 312.0

32767

7FFFH

> 593.6

32767

7FFFH

> 585.2

32767

7FFFH

Overflow

312.0

:

260.1

3120

:

2601

C30H

:

A29H

593.6

:

500.1

5936

:

5001

1730H

:

12D5H

585.2

:

533.3

5852

:

5333

16DCH

:

14D5H

Overshoot range

260.0

:

-200.0

2600

:

-2000

A28H

:

F830H

500.0

:

-328.0

5000

:

-3280

1389H

:

F330H

533.2

:

73.2

5332

:

732

14D4H

:

2DCH

Rated range

-200.1

:

-240.0

-2001

:

-2400

F82FH

:

F6A0H

-328.1

:

-400.0

-3281

:

-4000

F32FH

:

F060H

73.1

:

33.2

731

:

332

2DBH

:

14CH

Undershoot range

< - 240.0

-32768

8000H

< - 400.0

-32768

8000H

< 33.2

32768

8000H

Underflow

Representation of analog values for Cu 10 climatic and Cu 10, 50, 100 GOST climatic resistance thermometers

Table: Representation of analog values for Cu 10 climatic and Cu 10, 50, 100 GOST climatic resistance thermometers Representation of analog valuesfor resistance thermometers

Cu x0 climatic/in °C (1 digit = 0.01 °C)

Units

Cu x0 climatic in °F (1 digit = 0.01 °F)

Units

Range

dec

hex

dec

hex

> 180.00

32767

7FFFH

> 327.66

32767

7FFFH

Overflow

180.00

:

150.01

18000

:

15001

4650H

:

3A99H

327.66

:

280.01

32766

:

28001

7FFEH

:

6D61AH

Overshoot range

150.00

:

-50.00

15000

:

-5000

3A98H

:

EC78H

280.00

:

- 58.00

28000

:

-5800

6D60H

:

E958H

Rated range

-50.01

:

-60.00

-5001

:

-6000

EC77H

:

E890H

-58.01

:

-76.00

-5801

:

-7600

E957H

:

E250H

Undershoot range

< - 60.00

-32768

8000H

< - 76.00

-32768

8000H

Underflow

Representation of analog values for Cu 10, 50, 100, 500 GOST standard (0.00426) resistance thermometers

Table: Representation of analog values for Cu 10, 50, 100, 500 GOST standard (0.00426) resistance thermometers Representation of analog valuesfor resistance thermometers

Cu x0 Standard in °C (1 digit = 0.1°C)

Units

Cu x0 standard in °F (1 digit = 0.01 °F)

Units

Range

dec

hex

dec

hex

> 240.0

32767

7FFFH

> 464.0

32767

7FFFH

Overflow

240.0

:

200.1

2400

:

2001

0960H

:

07D1H

464.0

:

392.1

4640

:

3921

1220H

:

0F51H

Overshoot range

200.0

:

-50.0

2000

:

-500

07D0H

:

FE0CH

392.0

:

-58.0

3920

:

-580

0F50H

:

FDBCH

Rated range

-50.1

:

-60.0

-501

:

-600

FE0BH

:

FDA8H

-58.1

:

-76.0

-581

:

-760

FDBBH

:

FD08H

Undershoot range

< - 60.00

-32768

8000H

< - 76.0

-32768

8000H

Underflow

Representation of the analog values for Cu 10, 50, 100, 500 GOST standard (0.00428) resistance thermometers

Table: Representation of the analog values for Cu 10, 50, 100, 500 GOST standard (0.00428) resistance thermometers Representation of analog valuesfor resistance thermometers

Cu x0 standard in °C (1 digit = 0.01 °C)

Units

Cu x0 standard in °F (1 digit = 0.01 °F)

Units

Range

dec

hex

dec

hex

> 240.0

32767

7FFFH

> 464.0

32767

7FFFH

Overflow

240.0

:

200.1

2400

:

2001

0960H

:

07D1H

464.0

:

392.1

4640

:

3921

1220H

:

0F51H

Overshoot range

200.0

:

-200.0

2000

:

-2000

07D0H

:

F830H

392.0

:

-328.0

3920

:

-3280

0F50H

:

F330H

Rated range

-200.1

:

-240.0

-2001

:

-2400

F82FH

:

F6A0H

-328.1

:

-405.4

-3281

:

-4054

F32FH

:

F02AH

Undershoot range

< - 240.0

-32768

8000H

< - 405.4

-32768

8000H

Underflow

Representation of analog values for KTY83/110 silicon temperature sensors

Table: Representation of analog values for KTY83/110 silicon temperature sensors

KTY83/110 in °C
(1 digit = 0.1 °C)

Units

KTY83/110 in °F
(1 digit = 0.1 °F)

Units

KTY83/110 in °K
(1 digit = 0.1 °K)

Units

Range

dec

hex

dec

hex

dec

hex

> 206.3

32767

7FFFH

> 403.3

32767

7FFFH

> 479.5

32767

7FFFH

Overflow

206.3

:

175.1

2063

:

1751

080FH

:

06D7H

403.3

:

347.1

4033

:

3471

0FC1H

:

0D8FH

479.5

:

448.3

4795

:

4483

12BBH

:

1183H

Overshoot range

175

:

-55

1750

:

-550

06D6H

:

FDDAH

347

:

-67

3470

:

-670

0D8EH

:

FD62H

448.2

:

218.2

4482

:

2182

1182H

:

0886H

Rated range

-55.1

:

-64.7

-551

:

-647

FDD9H

:

FD79H

-67.1

:

-84.5

-671

:

-845

FD61H

:

FCB3H

218.1

:

208.5

2181

:

2085

0885H

:

08205H

Undershoot range

< -64.7

-32768

8000H

< -84.5

-32768

8000H

< 208.5

-32768

8000H

Underflow

Representation of analog values for KTY84/130 silicon temperature sensors

Table: Representation of analog values for KTY84/130 silicon temperature sensors

KTY84/130 in °C
(1 digit = 0.1 °C)

Units

KTY84/130 in °F
(1 digit = 0.1 °F)

Units

KTY84/130 in °K
(1 digit = 0.1 °K)

Units

Range

dec

hex

dec

hex

dec

hex

> 352.8

32767

7FFFH

> 667.0

32767

7FFFH

> 626.0

32767

7FFFH

Overflow

352.8

:

300.1

3528

:

3001

0DC8H

:

0BB9H

667.0

:

572.1

6670

:

5721

1A0EH

:

1659H

626.0

:

573.3

6260

:

5733

1874H

:

1665H

Overshoot range

300

:

-40

3000

:

-400

0BB8H

:

FE70H

572

:

-40

5720

:

-400

1658H

:

FE70H

573.2

:

233.2

5732

:

2332

1664H

:

091CH

Rated range

-40.1

:

-47.0

-401

:

-470

FE6FH

:

FE2AH

-40.1

:

-52.6

-401

:

-526

FE6FH

:

FDF2H

233.1

:

226.2

2331

:

2262

091BH

:

08D6H

Undershoot range

< -47.0

-32768

8000H

< -52.6

-32768

8000H

< 226.2

-32768

8000H

Underflow

Representation of the analog values of thermocouples type B

Table: Representation of the analog values of thermocouples type B Representation of analog valuesfor resistance thermometers

Type B in °C

Units

Type B in °F

Units

Type B in K

Units

Range

dec

hex

dec

hex

dec

hex

> 2070.0

32767

7FFFH

> 3276.6

32767

7FFFH

> 2343.2

32767

7FFFH

Overflow

2070.0

:

1820.1

20700

:

18201

50DCH

:

4719H

3276.6

:

2786.6

32766

:

27866

7FFEH

:

6CDAH

2343.2

:

2093.3

23432

:

20933

5B88H

:

51C5H

Overshoot range

1820.0

:

0.0

18200

:

0

4718H

:

0000H

2786.5

:

32.0

27865

:

320

6CD9H

:

0140H

2093.2

:

273.2

20932

:

2732

51C4H

:

0AACH

Rated range

:

-120.0

:

-1200

:

FB50H

:

-184.0

:

-1840

:

F8D0H

:

153.2

:

1532

:

05FCH

Undershoot range

< -120.0

-32768

8000H

< -184.0

-32768

8000H

< 153.2

32768

8000H

Underflow

Representation of the analog values of thermocouples type C

Table: Representation of the analog values of thermocouples type C Representation of analog valuesfor resistance thermometers

Type C in °C

Units

Type C in °F

Units

Range

dec

hex

dec

hex

> 2500.0

32767

7FFFH

> 3276.6

32767

7FFFH

Overflow

2500.0

:

2315.1

25000

:

23151

61A8H

:

5A6FH

3276.6

:

2786.6

32766

:

27866

7FFEH

:

6CDAH

Overshoot range

2315.0

:

0.0

23150

:

0

5A6EH

:

0000H

2786.5

:

32.0

27865

:

320

6CD9H

:

0140H

Rated range

-0.1

:

-120.0

-1

:

-1200

FFFFH

:

FB50H

31.9

:

-184.0

319

:

-1840

013FH

:

F8D0H

Undershoot range

< -120.0

-32768

8000H

< -184.0

-32768

8000H

Underflow

Representation of the analog values of thermocouples type E

Table: Representation of the analog values of thermocouples type E Representation of analog valuesfor resistance thermometers

Type E in °C

Units

Type E in °F

Units

Type E in K

Units

Range

dec

hex

dec

hex

dec

hex

> 1200.0

32767

7FFFH

> 2192.0

32767

7FFFH

> 1473.2

32767

7FFFH

Overflow

1200.0

:

1000.1

12000

:

10001

2EE0H

:

2711H

2192.0

:

1832.2

21920

:

18322

55A0H

:

4792H

1473.2

:

1273.3

14732

:

12733

398CH

:

31BDH

Overshoot range

1000.0

:

-270.0

10000

:

-2700

2710H

:

F574H

1832.0

:

-454.0

18320

:

-4540

4790H

:

EE44H

1273.2

:

0

12732

:

0

31BCH

:

0000H

Rated range

< -270.0

< -2700

< F574H

< -454.0

< -4540

<EE44H

<0

<0

<0000H

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at...

 

... from F0C4H underflow and outputs 8000H.

... from FB70H underflow and outputs 8000H.

... from E5D4H underflow and outputs 8000H.

 

Representation of the analog values of thermocouples type J

Table: Representation of the analog values of thermocouples type J Representation of analog valuesfor resistance thermometers

Type J in °C

Units

Type J in °F

Units

Type J in K

Units

Range

dec

hex

dec

hex

dec

hex

> 1450.0

32767

7FFFH

> 2642.0

32767

7FFFH

> 1723.2

32767

7FFFH

Overflow

1450.0

:

1200.1

14500

:

12001

38A4H

:

2EE1H

2642.0

:

2192.2

26420

:

21922

6734H

:

55A2H

1723.2

:

1473.3

17232

:

14733

4350H

:

398DH

Overshoot range

1200.0

:

-210.0

12000

:

-2100

2EE0H

:

F7CCH

2192.0

:

-346.0

21920

:

-3460

55A0H

:

F27CH

1473.2

:

63.2

14732

:

632

398CH

:

0278H

Rated range

< -210.0

< -2100

<F7CCH

< -346.0

< -3460

<F27CH

< 63.2

< 632

< 0278H

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...

 

... from F31CH underflow and outputs 8000H.

... from EA0CH underflow and outputs 8000H.

... from FDC8H underflow and outputs 8000H.

 

Representation of the analog values of thermocouples type K

Table: Representation of the analog values of thermocouples type K Representation of analog valuesfor resistance thermometers

Type K in °C

Units

Type K in °F

Units

Type K in K

Units

Range

dec

hex

dec

hex

dec

hex

> 1622.0

32767

7FFFH

> 2951.6

32767

7FFFH

> 1895.2

32767

7FFFH

Overflow

1622.0

:

1372.1

16220

:

13721

3F5CH

:

3599H

2951.6

:

2501.8

29516

:

25018

734CH

:

61BAH

1895.2

:

1645.3

18952

:

16453

4A08H

:

4045H

Overshoot range

1372.0

:

-270.0

13720

:

-2700

3598H

:

F574H

2501.6

:

-454.0

25061

:

-4540

61B8H

:

EE44H

1645.2

:

0

16452

:

0

4044H

:

0000H

Rated range

< -270.0

< -2700

< F574H

< -454.0

< -4540

<EE44H

< 0

< 0

< 0000H

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...

 

... from F0C4H underflow and outputs 8000H.

... from E5D4H underflow and outputs 8000H.

... from FB70H underflow and outputs 8000H.

 

Representation of the analog values of thermocouples type L

Table: Representation of the analog values of thermocouples type L Representation of analog valuesfor resistance thermometers

Type L in °C

Units

Type L in °F

Units

Type L in K

Units

Range

dec

hex

dec

hex

dec

hex

> 1150.0

32767

7FFFH

> 2102.0

32767

7FFFH

> 1423.2

32767

7FFFH

Overflow

1150.0

:

900.1

11500

:

9001

2CECH

:

2329H

2102.0

:

1652.2

21020

:

16522

521CH

:

408AH

1423.2

:

1173.3

14232

:

11733

3798H

:

2DD5H

Overshoot range

900.0

:

-200.0

9000

:

-2000

2328H

:

F830H

1652.0

:

-328.0

16520

:

-3280

4088H

:

F330H

1173.2

:

73.2

11732

:

732

2DD4H

:

02DCH

Rated range

< -200.0

< -2000

< F830H

< -328.0

< -3280

< F330H

< 73.2

< 732

<02DCH

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...

 

... from F380H underflow and outputs 8000H.

... from EAC0H underflow and outputs 8000H.

... from FE2CH underflow and outputs 8000H.

 

Representation of the analog values of thermocouples type N

Table: Representation of the analog values of thermocouples type N Representation of analog valuesfor resistance thermometers

Type N in °C

Units

Type N in °F

Units

Type N in K

Units

Range

dec

hex

dec

hex

dec

hex

> 1550.0

32767

7FFFH

> 2822.0

32767

7FFFH

> 1823.2

32767

7FFFH

Overflow

1550.0

:

1300.1

15500

:

13001

3C8CH

:

32C9H

2822.0

:

2372.2

28220

:

23722

6E3CH

:

5CAAH

1823.2

:

1573.3

18232

:

15733

4738H

:

3D75H

Overshoot range

1300.0

:

-270.0

13000

:

-2700

32C8H

:

F574H

2372.0

:

-454.0

23720

:

-4540

5CA8H

:

EE44H

1573.2

:

0

15732

:

0

3D74H

:

0000H

Rated range

< -270.0

< -2700

< F574H

< -454.0

< -4540

<EE44H

< 0

< 0

< 0000H

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...

 

... from F0C4H underflow and outputs 8000H.

... from E5D4H underflow and outputs 8000H.

... from FB70H underflow and outputs 8000H.

 

Representation of the analog values of thermocouples type R, S

Table: Representation of the analog values of thermocouples type R, S Representation of analog valuesfor resistance thermometers

Type R, S in °C

Units

Type R, S in °F

Units

Types R, S in K

Units

Range

dec

hex

dec

hex

dec

hex

> 2019.0

32767

7FFFH

> 3276.6

32767

7FFFH

> 2292.2

32767

7FFFH

Overflow

2019.0

:

1769.1

20190

:

17691

4EDEH

:

451BH

3276.6

:

3216.4

32766

:

32164

7FFEH

:

7DA4H

2292.2

:

2042.3

22922

:

20423

598AH

:

4FC7H

Overshoot range

1769.0

:

-50.0

17690

:

-500

451AH

:

FE0CH

3216.2

:

-58.0

32162

:

-580

7DA2H

:

FDBCH

2042.2

:

223.2

20422

:

2232

4FC6H

:

08B8H

Rated range

-50.1

:

-170.0

-501

:

-1700

FE0BH

:

F95CH

-58.2

:

-274.0

-582

:

-2740

FDBAH

:

F54CH

223.1

:

103.2

2231

:

1032

08B7H

:

0408H

Undershoot range

< -170.0

-32768

8000H

< -274.0

-32768

8000H

< 103.2

< 1032

8000H

Underflow

Representation of the analog values of thermocouples type T

Table: Representation of the analog values of thermocouples type T

Type T in °C

Units

Type T in °F

Units

Type T in K

Units

Range

dec

hex

dec

hex

dec

hex

> 540.0

32767

7FFFH

> 1004.0

32767

7FFFH

> 813.2

32767

7FFFH

Overflow

540.0

:

400.1

5400

:

4001

1518H

:

0FA1H

1004.0

:

752.2

10040

:

7522

2738H

:

1D62H

813.2

:

673.3

8132

:

6733

1FC4H

:

1AADH

Overshoot range

400.0

:

-270.0

4000

:

-2700

0FA0H

:

F574H

752.0

:

-454.0

7520

:

-4540

1D60H

:

EE44H

673.2

:

3.2

6732

:

32

1AACH

:

0020H

Rated range

< -270.0

< -2700

< F574H

< -454.0

< -4540

<EE44H

< 3.2

< 32

< 0020H

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...

 

... from F0C4H underflow and outputs 8000H.

... from E5D4H underflow and outputs 8000H.

... from FB70H underflow and outputs 8000H.

 

Representation of the analog values of thermocouples type U

Table: Representation of the analog values of thermocouples type U Representation of analog valuesfor resistance thermometers

Type U in °C

Units

Type U in °F

Units

Type U in K

Units

Range

dec

hex

dec

hex

dec

hex

> 850.0

32767

7FFFH

> 1562.0

32767

7FFFH

> 1123.2

32767

7FFFH

Overflow

850.0

:

600.1

8500

:

6001

2134H

:

1771H

1562.0

:

1112.2

15620

:

11122

2738.0H

:

2B72H

1123.2

:

873.2

11232

:

8732

2BE0H

:

221CH

Overshoot range

600.0

:

-200.0

6000

:

-2000

1770H

:

F830H

1112.0

:

-328.0

11120

:

-3280

2B70H

:

F330H

873.2

:

73.2

8732

:

732

221CH

:

02DCH

Rated range

< -200.0

< -2000

< F830H

< -328.0

< -3280

< F330H

< 73.2

< 732

<02DCH

Underflow

Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...

 

... from F380H underflow and outputs 8000H.

... from EAC0H underflow and outputs 8000H.

... from FE2CH underflow and outputs 8000H.

 

Representation of analog values for type TXK/XKL GOST thermocouple

Table: Representation of analog values for type TXK/XKL GOST thermocouple

Type TXK/XKL

in °C

Units

Type TXK/XKL

in °F

Units

Range

dec

hex

dec

hex

> 1050.0

32767

7FFFH

> 1922.0

32767

7FFFH

Overflow

1050.0

:

800.1

8500

:

8001

2904H

:

1F41H

1922.0

:

1472.1

19220

:

14721

4B14H

:

3981H

Overshoot range

800.0

:

0.0

:

-200.0

8000

:

0

:

-2000

1F40H

:

0000H

:

F830H

1472.0

:

32.0

:

-328.0

14720

:

320

:

-3280

3980H

:

0140H

:

F330H

Rated range

< -200.0

<-32768

< F8000H

< -328.0

<-32768

8000H

Underflow



 

Unterstützung zur Statistik
Mit dieser Funktion werden die IDs des Suchergebnisses nach gewünschter Anzahl ausgegeben (Format .txt)

Liste generieren
URL kopieren
Diese Seite in neuem Design anzeigen
mySupport Cockpit