Dear Experts, I want to migrate a project from Step 7 v5.5 to TIA.I tried the built in tool of TIA but it ends with errors. Can anyone tell me the steps of migrating a project??
|
Kashir Saeed. |
|
This contribution was helpful to
3 thankful Users |
5/23/2014 9:47 AM | |
Joined: 8/27/2010 Last visit: 4/13/2024 Posts: 417 Rating:
|
Hi! Hereyou can find complete guide of migration to TIA. There is a list of requirements and list of non-migratable components. Check it and if you can find a solution, provide more details about errors. Hope it helps. |
This contribution was helpful to
5 thankful Users |
5/23/2014 3:45 PM | |
Posts: 510 Rating:
|
Your Step 7 5.5 project has to be consistent beforeit can be migrated. Right click on the blocks folder in SIMATIC Manager and select Check Block Consistency. In the Editor that opens up, select File, Compile all. If there are errors, fix the errors and compile all again until there are no errors. Also there are options in Step 7 like PDiag that aren't yet supported in Portal. Also 300T processors and 400H systems are not supported. Good Luck, Bill |
This contribution was helpful to
4 thankful Users |
5/23/2014 5:57 PM | |
Posts: 107 Rating:
|
you must compile ur s7 project using simatic manager to be sure it doesn't contain any warning or errors, then do following 1-Setup your TIA version, open it. 2-on left,you will find Migrate project tab 3-select your s7 project path. 4-you must have licence of Step 7 V5.5 to complete migration.
|
This contribution was helpful to
2 thankful Users |
5/23/2014 6:23 PM | |
Posts: 510 Rating:
|
One more thing, the default loacation for the migrated project is in the Step 7 folder with the V5.5 project. You may want to select the Automation folder which is the default loacation for TIA Portal projects. That way you can find it later. Check the hardware to make sure that nothing is missing and don't forget to compile the PLC after migration. Good Luck, billwest |
3/3/2015 1:40 PM | |
Posts: 22 Rating:
|
Hi I have tried to migrate but the TIA portal doesn't recognise the s7p project file as adviced in this post https://support.industry.siemens.com/cs/#document/62100731?lc=en-WW it only recognise the files .am13 and .hmi as shown in the screenshot. Yasmeen |
3/3/2015 1:57 PM | |
Joined: 8/11/2014 Last visit: 3/12/2018 Posts: 33 Rating:
|
Hi, do you have installed STEP7 V5.5 or Professional 2010? You need it to migrate, without it doesn´t work. Best would be, if you have it installed on the same PG/PC like TIA Portal is installed to. If it is not on the same PG/PC you can convert it to a TIA compatible migrate-format: |
Last edited by: BWayne at: 3/3/2015 1:58:20 PMLast edited by: BWayne at: 3/3/2015 1:59:09 PM |
|
This contribution was helpful to
2 thankful Users |
7/12/2016 8:02 PM | |
Posts: 1 Rating:
|
HOW TO I FIX IT |
7/12/2016 8:29 PM | |
Joined: 1/21/2013 Last visit: 11/20/2024 Posts: 4620 Rating:
|
Hello, You have installed on PC STEP 7 "classic" V5.4 or V5.5? |