8/29/2014 10:11 AM | |
Posts: 10 Rating: (1) |
Hibg2492 Still cant connect to data server. I tried to put a circle and force 1 from PLC. The circle color should be green (1 is ON) but yet nothing happened. But when I tried to simulate let say LT101 Value in PLC, the value showed up in WinCC. Any solution guys? I use TCP/IP |
Last edited by: Ery at: 8/29/2014 10:19 AMLast edited by: Ery at: 8/29/2014 10:11 AM |
|
8/29/2014 2:57 PM | |
Posts: 10 Rating: (1) |
Hibg2492/Georg Berghof Thanks for your reply. Nope its not running during runtime, not even in Windows Task maager (Process). Is there anywaay to fix this thing? My PC is 64 bit Thanks
|
Last edited by: Ery at: 8/29/2014 2:58 PM |
|
8/30/2014 12:57 PM | |
Joined: 5/16/2014 Last visit: 9/12/2022 Posts: 7298 Rating: (2145) |
Hello Ery, You have activeted the Alarmlogging in the startuplist. If the process CCAlgRtServer.exe does not exist in the list of processes, it seems to crash immediately after the start. You should watch the process with AdPlus to get an userdump. The create a Support Request and send the dump to the Technical Support. For using AdPlus see http://support.automation.siemens.com/WW/view/en/45020870 Regards Georg Berghof |
PS: If this post did really help you, you may use the Rate-button |
|