Hello What is the best and most practical and cost effeciant way to communicate S7-1200 to a BMS system like Desigo CC over BACNET? Thank you |
| 4/28/2017 9:49 AM | |
|
Joined: 12/29/2008 Last visit: 9/12/2025 Posts: 24 Rating:
|
Very simple solution, it is to use MODBUS TCP on S71200 and gateway Fieldserver MODBUS BACNET TCP You can find it here: Gateway BACNET-MODBUS Very simple to configure and to use. |
This contribution was helpful to
|
|
| 8/2/2017 8:35 AM | |
|
Posts: 8171 Rating:
|
New question published by andres.sandoval.1984 is split to a separate thread with the subject Is it possible to get information of Bacnet devices from two PLC through of Gateway UGW Micro Profinet? . Best regards |