11/22/2016 1:28 PM | |
Posts: 1 Rating:
|
Dear Sir, I need your help to solve my problem with Analog Output card. Before we used 6ES5 470-8MB12 but now was broken. Can we change with 6ES5 470-8MC12. Can this card used same function. If can, are there any changing with setting or program for Address Analog Output. Sulistiyo Heri ------------------------------------------------------------------------------------------ |
Last edited by: Min_Moderator at: 11/24/2016 12:51:22 PMNew subject after splitting |
|
11/22/2016 2:25 PM | |
Joined: 9/27/2006 Last visit: 9/19/2025 Posts: 12415 Rating:
|
Hello Irwanto; Have a look at this page from an old ST50 Catalog (for S5 modules): https://w3.siemens.com/automation/jp/Documents/9_SIMATIC_S5_catalog_ST50_en.pdf Note that the -8MB12 is designed for ±20 mA signals, and the -8MC12 connects to 4-20 mA current inputs. You could eventually replace one by another, if the signal you are reading is unipolar (only positve signal), and with a reduced range (and accuracy). Or use a signal converter to transform the input signal fronm your sensor from ±20 mA to 4-20 ma before connecting to the new analog module. Hope this helps, Daniel Chartier |
Last edited by: dchartier at: 11/22/2016 2:26:29 PM |
|