hi, you are using a CP343-1 to communcate over Profinet. Therefor you need other blocks. See this FAQ: How do you program communication blocks FC11 and FC12 for the PROFINET IO controller? I guess the SFC14 and SFC15 are not on this CPU because of the CPU can not perform an own DP- or/and PN-system. It has only interfaces for PtP communication. hope this helps, regards, |
Last edited by: mopS04 at: 8/9/2017 1:16:04 PM |
|
| 8/9/2017 5:09 PM | |
|
Posts: 15 Rating:
|
Thank you so much! I will try and inform you soon. |