Hi all, I have some problem, I want to upload program from CPU 317F-2 PN/DP to PC , for backup , and error occur. software using Step7 v5.5 sp4. s7 FConsfigurasiPack v5.5 sp9 error still occur. please, anyone give me solution for my problem. thanks. ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 11/27/2017 7:37:44 AMNew subject after splitting |
|
| 11/26/2017 7:47 PM | |
|
Joined: 3/28/2015 Last visit: 1/4/2026 Posts: 727 Rating:
|
Hello, Kindly have a look at the following FAQ: What is the meaning of the error codes (xxxx:yyyy) in STEP 7? Error number: 13:77 Text: While interpreting the system data blocks (SDBs) uploaded from the module, an error was recognized in the programming device and processing halted. Cause: 1-Inconsistent HW configuration in module, occurs when previous loading of SDBs into the module was incomplete or faulty. 2-Options package for configuring specific modules (e.g. CPs) is not installed.
|
Last edited by: Jen_Moderator at: 11/27/2017 7:40:48 AMInserted right link. Eng.Mohamed Ibrahim |
|