(2)| 1/26/2013 2:28 PM | |
|
Joined: 8/31/2010 Last visit: 12/6/2025 Posts: 1525 Rating:
|
Hello ARN2011, AttachmentE:\ModbusTCPIP.pdf (3920 Downloads) |
|
Like it? Rate it! |
|
| 1/28/2013 7:20 AM | |
|
Joined: 7/16/2011 Last visit: 8/16/2024 Posts: 24 Rating:
|
Hello UMENCHO |
| 2/2/2013 4:45 PM | |
|
Joined: 7/16/2011 Last visit: 8/16/2024 Posts: 24 Rating:
|
Dear Yolov, Thank you for your post. So it shows it will be possible to connect to non-modicon PLC's. Best regards |
| 7/3/2017 11:46 AM | |
|
Posts: 8171 Rating:
|
New question published by H.M.Suleman is split to a separate thread with the subject How many Modbuses can create in tag management?. Best regards |
| 7/17/2017 11:20 PM | |
|
Joined: 3/19/2010 Last visit: 6/15/2025 Posts: 439 Rating:
|
Hi, As you could see from others people answers, there is no guarantee that Modbus TCP driver from the WinCC will work with non-Modicon (Schneider) PLC's. Some devices that fit the protocol, will work. Some others - will not. However, some OPC server with Modbus TCP connection solves the problem. OPC's of this kind are usually not for free, but I have found several very, very cheap solution, easy to engineering, and reliable. I am sharing one with you, that saved my life :) http://www.lectussoft.com/
Best regard, |