Hello.... Alarm 300501 "maximum current monitoring" 1.Serious fault occured during the actual current measurement. 2. maximum current thershold was exceeded while the rotor positionientifaiction was active(Feed Drive Only) Check the IGBTS of the power module 80A by keeping the multimeter in diode mode. I am attaching you the details. check it out... AttachmentChecking procedure for FDD-MSD Module.pdf (783 Downloads) |