Thanks for reply, i take some pictures about my configuration. The thing is that I have 2 panels and just one IODB is generated automatically (the one is attached to the CPU Profinet Interface), have you used MP277F through CP343-1 Advanced or any other CP? I wanted to know why the IO DB is not automatically generated when the pannel its connected to the CP343-1 and in any case if there is another way to make this IO DB by hand or if i am missing any configuration in the CP343-1. AttachmentImagenes.zip (73 Downloads) |
| 2/1/2013 5:19 PM | |
|
Joined: 5/27/2009 Last visit: 8/27/2025 Posts: 122 Rating:
|
After doing some test with HW Configuration and reading CPs characteristics in catalog...now i think its not possible toestablish profisafe communication using CP343-1 Advanced, thats why the F-I/O DB was not generated. I tried using a CPU 416F-2 + CP 443-1 and with this configurationthe DB was automatically generated just like with CPU 317F-2 PN/DP. My conclusion is that i have to try with another CPU-F with PN interface integrated Like a Tip, the MP277F Library can be downloades from here: https://support.automation.siemens.com/WW/llisapi.dll?query=Profisafe&func=cslib.cssearch&content=adsearch%2Fadsearch.aspx%3Ftab%3D2&lang=en&siteid=csius&objaction=cssearch&searchinprim=_searchinprim_&nodeid=99&x=16&y=8&cssearchengine=NEW |