hi guys.. I need to connect siemens logo plc with any other serial (RS 485) support plc from other company. If AB 1400 plc support both serial and TCP/IP so can i connect with my logo oba8 and AB1400..? sorry for my bad English. Thanks in advance.. ------------------------------------------------------------------------------------------ |
Last edited by: Min_Moderator at: 12/21/2015 10:29:30 AMNew subject after splitting |
|
| 12/20/2015 11:13 AM | |
|
Joined: 12/18/2014 Last visit: 12/24/2025 Posts: 36371 Rating:
|
No. Logo supports only TCP/IP with S7-200 protocol, no RS485 or other. |