Hello, I have not tried using Power Supply modules with different MLFBs on an H-Redundant system.I can not suggest using "6ES7 407-0KA02-0AA0" instead of "6ES7 407-0KR02-0AA0"."PS 10A R" is redundant capable while "PS 407 10A" doesn't support that.
To confirm, please ask it from HERE. I hope this helps, Hamid Hosseini |
This contribution was helpful to2 thankful Users |
9/6/2014 3:24 PM | |
Joined: 10/24/2011 Last visit: 3/9/2023 Posts: 257 Rating: (1) |
Ya, I saw it in Hardware config. explaination. Thanks, Shailesh
|