Import of a technical question from the user mr.adi
|
8/31/2015 11:57 AM | |
Posts: 739 Rating: (55)
|
Please have a look into the List manual. There you´ll find a brief description of F0022 https://support.industry.siemens.com/cs/ww/en/view/23708204 F0022 Hardware monitoring activeThis fault (r0947 = 22 and r0949 = 1) occurs under the following circumstances: (1) DC link overcurrent condition = IGBT short-circuit (2) Braking chopper short-circuit (3) Ground fault (4) I/O module not correctly inserted or defect FAQ: https://support.industry.siemens.com/cs/ww/en/view/13533329
|