Hi, from the documentation https://support.automation.siemens.com/WW/llisapi.dll/csfetch/67423513/siemense_Operate_27SP3HF4_PC.pdf?func=cslib.csFetch&nodeid=67702536 The screen size of Operate on the PC monitor can be set in the file <installationdirectory>\user\sinumerik\hmi\cfg\slrs.ini: [Global] Resolution = ; Permissible values: 640x480, 800x600, 1024x768, 1280x1024 |
This contribution was helpful to1 thankful Users |
1/17/2018 9:58 AM | |
Posts: 29 Rating: (1) |
Also have to change in systemconfiguration.ini: adaptHmiResolutionToActiveUnit=false |