Hi, I'm also facing slownes issue.In my project write request is 27735. I want to know is it reason for slownes ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 03/19/2020 10:57:46New subject after splitting |
|
3/19/2020 9:30 AM | |
Joined: 5/16/2014 Last visit: 9/12/2022 Posts: 7298 Rating: (2164)
|
Hello Drj123@123, if you have 27735 open Write request, this is the reason, You have a massive communication problem. Which PLCs do yuo use ? For S7-300/400 check "SIMATIC_S7_PROTOCOL_SUITE_0x.LOG"
Georg Berghof |