Actually I think you're not doing something wrong at all. Do you reset the EXECUTE input when DONE or ERROR are set to TRUE? If so, you'll only see DONE or ERROR for one cycle of the PLC program. Here's a small example on how to handle the Ident blocks with RF600 reader: |