Hello, it is possible to use 5.9.2 TM Count 1x24V / TM Count 2x24V or 5.9.3 TM PosInput 1 / TM PosInput 2 for TTL or SSI encoder. https://support.industry.siemens.com/cs/ww/en/view/109749262 Direct combination between S210 is not possible. You need a PLC. Configuring Technology Objects with SIMATIC S7 1500 and SINAMICS S210 in TIA-Portal https://support.industry.siemens.com/cs/ww/en/view/109749795 |