2/3/2021 5:10 PM | |
Joined: 3/11/2019 Last visit: 9/18/2024 Posts: 3 Rating: (0) |
Hello SpikeStart any solution for your problem? I'm asking becouse I'm facing the same problem exectly with your configuration Thanks ------------------------------------------------------------------------------------------ |
Last edited by: Jen_Moderator at: 02/11/2021 09:51:52New subject after splitting |
|
2/5/2021 10:18 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877) |
Hello, What is your problem? Expert 0_Einstein & ChristophD has explained it clearly. Provide external 24 V supply to CU & DO output common incase if you want DO status to be check/use when PM supply is OFF. HTH |
2/11/2021 9:52 AM | |
Joined: 6/19/2017 Last visit: 9/6/2024 Posts: 8175 Rating: (172) |
Closed cause question posted twice. The second thread with the subject F30040 S120 PM240-2 CU310-2 is published within the conference SINAMICS. Jen_Moderator |
Follow us on