9/21/2017 8:52 PM | |
Posts: 32 Rating:
|
Hi everyone, I have an issue in adding a new device. I imported 7sj85 driver 7.50 and in adding the short code, I can't pass the step 4 communication configuration that says no configuration available. Install a device driver DDD for communication first. Thank you. |
9/21/2017 9:51 PM | |
Joined: 9/27/2006 Last visit: 3/28/2025 Posts: 12344 Rating:
|
Hello Amahrit; Sometimes these messages in Siemens software can be frustrating, i understand. But basically you have to trust them, take them literally, and act on them. If DIGSI 5 is telling you that you must load DDD files for communication drivers before continuing the installation, try locating these files and loading them, as requested... They are generally easy to find, searching the web, For example: Googling DIGSI DDD files takes you here: SIPROTEC 5 and DIGSI 5 Downloads - Digital Grid - SiemensAt the bottom of the available selections you will find Device Drivers for DIGSI-DDD. Hope this helps, Daniel Chartier |
Last edited by: dchartier at: 9/21/2017 9:53:52 PM |
|
9/21/2017 10:01 PM | |
Posts: 32 Rating:
|
Thank you dchartier for your answer. I had already downloader DDD files and import them by using Tools->Import device drivers and I selected the DDD files but still the same problem. |
9/22/2017 10:20 AM | |
Joined: 10/9/2007 Last visit: 3/17/2025 Posts: 1259 Rating:
|
Hi you have to install the DDD for communication as well |
Energy Automation products: Sicam, Siprotec, Digsi |
|
This contribution was helpful to
1 thankful Users |
9/22/2017 1:57 PM | |
Joined: 9/27/2006 Last visit: 3/28/2025 Posts: 12344 Rating:
|
Hello Amahrit; This document explains how to use the Siprotec relay keys to determine the existing versions of Devoce Drivers for DIGSI so you can determine which versions you must load on the relay. Hope this helps, Daniel Chartier |
9/26/2017 11:04 AM | |
Posts: 2 Rating:
|
Hello Amahrit! I have the same problem. Have you solved this problem? |
9/27/2017 5:31 PM | |
Posts: 32 Rating:
|
Hello everyone, Thank you Mike J, I have installed communication DDD and it worked. |
This contribution was helpful to
1 thankful Users |
9/28/2017 3:57 AM | |
Posts: 2 Rating:
|
I have solved this problem by installed Protocols in COM-DDD folder. Thanks to Amahrit and Mike J. |
11/4/2017 5:27 PM | |
Posts: 1 Rating:
|
hello i have this problem step 4 and i have downloaded all device drivers and installed them would you guide me to solve this problem |
3/20/2018 11:17 AM | |
Posts: 2 Rating:
|
Hi, I solved the situation with: --> Tools-->Import device drivers --> import file: Protocols_FW-V07.54_CFG-V07.54_DDD-V07.54.ddd and --> import file: Protocols_FW-V07.50_CFG-V07.50_DDD-V07.50.ddd This files is in below link (for my IED): https://support.industry.siemens.com/cs/document/109749004/siprotec-5-7sa87-7sd87-7sl87-7vk87-digsi-device-drivers-v7-5x-?dti=0&pnid=24249&lc=en-WW Good work, |
This contribution was helpful to
1 thankful Users |