11/13/2011 10:11 AM | |
Joined: 5/28/2008 Last visit: 1/17/2021 Posts: 4193 Rating:
|
Hello Sazzad, Please install a mesuring device like a power meter to monitor voltage fluctuations along 24 hr/day. I am very much sure that the problem is comming from the fluctuations and it is very important to have a record for the problem in order to avoid more MM4 failures. And I do recommend not to install more MM4 drives withoutLine commutating chocke
Attached a document that show you in a simple way how to measure % line impedance.
AttachmentAppsNote10.pdf (462 Downloads) |
Ayman Elotaify |
|
11/14/2011 1:09 AM | |
Posts: 3 Rating:
|
thanks. i will try by your way. regards sazzad |