Hi, the parameters for the CUFC are not the same as on the modern CUVC. Please see the attached operating instructions, you can inititate a factory reset using P052=1. I had a quick look, and I don't think there was a lock and key on this early model. Note, check the access level P051=3 (Expert) and P053 (Access by . . . . eg PMU/OP1S) the value 6 is a safe bet, this enables access by all usual means. Regards, Graeme