8/5/2016 1:11 PM | |
Posts: 81 Rating:
|
Dear Sir/Madam, I have installed TIA Portal V13 SP1 and WinCC Professional V13 SP1 (512) and then also installed WinCC Professional RT (512). When I add a PC runtime system the start RT button is still grayed out (inactive). I have attached pictures of installed software, license and the problem.. Can anyone please help. I could see this issue in other forums but could not find an answer.. Thank you, Regards, Haris AttachmentWinCC Complaint.zip (289 Downloads) |
8/5/2016 2:03 PM | |
Joined: 5/12/2006 Last visit: 4/4/2025 Posts: 22607 Rating:
|
Hello, this is ok because this button is only working with WinCC RT Advanced/Panel Systems and not with WinCC RT Professional.
Christoph |
8/5/2016 3:21 PM | |
Posts: 81 Rating:
|
Dear Sir, Thank you for responding and helping out. If this is disables in the RT / then how can we start the RT? |
8/5/2016 3:40 PM | |
Joined: 5/12/2006 Last visit: 4/4/2025 Posts: 22607 Rating:
|
Hello, transfer the RT from the engineering to Filesystem and start the RT from the location. Regards Christoph |
8/6/2016 7:36 PM | |
Posts: 81 Rating:
|
Hi, I tried that, it works - but it runs just like it runs if you simulate it. Moreover, it runs in a small screen window.. is there a way to re-adjust the screen size or run full screen - I miss Wincc Flexible :( |
8/8/2016 11:54 AM | |
Joined: 9/3/2008 Last visit: 3/24/2025 Posts: 933 Rating:
|
Isn't it a good thing that the simulation runs just like the real thing ;-) The screen size can of course be adjusted, but for WinCC Professional it is done differently since it is a different product. This is to be expected. If you go open "Runtime settings" you will find the "General" where you select the start picture. If you then go to "Screen" settings, this is where you can select "Full screen" under the "Properties" settings. When you edit the Picture itself, you can go to "Properties -> Properties" and select "Layout" for the Picture (Screen). Here you can also set the Width / Height of the actual picture. |
Michael |
|
11/9/2016 8:29 AM | |
Posts: 4 Rating:
|
Hello, i wrote a message yesterday. I have a plc 1214 dc dc rly and a want to use my pc to be a hmi. i have v13 tia portal and advanced win cc.i set the pg/pc settings tcp ip.1 but the run time button is grey.Please help me. I coludnt solve this problem for a week. Best Regards |
11/9/2016 8:42 AM | |
Joined: 5/12/2006 Last visit: 4/4/2025 Posts: 22607 Rating:
|
then look here, this is your topic with the answers! https://support.industry.siemens.com/tf/ww/en/posts/how-to-see-if-t-the-panel-program-runs/157336/?page=0&pageSize=10 |
This contribution was helpful to
1 thankful Users |