12/4/2019 10:36 AM | |
Posts: 10 Rating: (0) |
|
Last edited by: SDGADHE at: 12/04/2019 10:38:43 |
|
12/4/2019 10:37 AM | |
Posts: 10 Rating: (0) |
|
12/4/2019 11:17 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877)
|
Please check NC start up switch S3 position & confirm it is at 0. In attached snap it is not clearly visible. |
12/4/2019 11:23 AM | |
Posts: 10 Rating: (0) |
Yes sir, S4 and S3 both in "0" position |
12/4/2019 11:29 AM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877)
|
Please check 611D drive. Either there is problem with drive or drive data can not be loaded. Please try to clear NC/PLC data & reload. Procedure for it is same or you can search here. |
12/4/2019 12:02 PM | |
Posts: 10 Rating: (0) |
Thank you for reply. Let me know, SF (system fault) led should be ON or OFF after NC/PLC data clear ? |
12/4/2019 12:09 PM | |
Joined: 4/23/2010 Last visit: 12/31/2023 Posts: 8092 Rating: (877)
|
When S3 & S4 switch position is at 0, NCU seven segment displays 6, PR LED is GREEN, SF must be OFF. |