5/23/2019 10:08 AM | |
Posts: 1283 Rating: (105) |
Did you check the service mode whether excitataion is ON or OFF. i was able to edit the correction factor. could you share some pics? |
5/23/2019 1:46 PM | |
Posts: 2 Rating: (0) |
I checked excitation mode is on. There was mis typing in my question. What I want know is how to change "Calibration factor" and "Excitation Frequency". |
5/23/2019 1:48 PM | |
Posts: 1283 Rating: (105) |
I think it's normal to be not able to change it. Even for me it's the same |
5/28/2019 2:21 PM | |
Posts: 10 Rating: (0) |
Hi, You can't change Calibration Factor, only thing you can play around is Correction Factor from 0.85 to 2. Regarding Excitation Freq, you can select from preconfigured available in menu only. Attached sheet from manual for Sensor Characteristics. Regards, Davinder Singh AttachmentSensor Characteristics.pdf (309 Downloads) |