9/28/2016 10:07 AM | |
Joined: 3/5/2014 Last visit: 8/5/2022 Posts: 5521 Rating: (1050) |
hi, how do you measure that? do you have a 2-wire or a 4-wire transducer? how is it connected? Have a look in the manual, how to connect it, chapter 6.7: SIMATIC S7-300 S7-300 Module data hope this helps, regards, |
FCK WAR! |
|
9/28/2016 10:12 AM | |
Joined: 8/29/2016 Last visit: 12/18/2017 Posts: 29 Rating: (0) |
Hi, i take the measure by a multimeter. its a 2-wire , i do the wiring following the manual ( CH0 two terminals ) nothing on the other CHs , desactivated from software . thanks for the reply |
9/28/2016 1:28 PM | |
Joined: 3/5/2014 Last visit: 8/5/2022 Posts: 5521 Rating: (1050) |
ok,I got the manual: SIPART PS2 (6DR5...)
|
FCK WAR! |
|
9/28/2016 1:40 PM | |
Joined: 8/29/2016 Last visit: 12/18/2017 Posts: 29 Rating: (0) |
a WEKA cryo valve . |
9/28/2016 1:41 PM | |
Joined: 3/5/2014 Last visit: 8/5/2022 Posts: 5521 Rating: (1050) |
oh, I mean what pins are connected on SIPART-side to the SM331? |
FCK WAR! |
|
9/28/2016 1:50 PM | |
Joined: 8/29/2016 Last visit: 12/18/2017 Posts: 29 Rating: (0) |
ah sorry ! 61 and 62 for feedback |