I am having trouble adding DTM for LR560 to Pactware. The guides and online files suggest I install Sitrans DTM 4.00 Link:https://support.industry.siemens.com/cs/ww/en/view/109484287 and the install the EDD https://support.industry.siemens.com/cs/ww/en/view/60441214 After that I need to do a catalog update in Pactware, but I always receive the message: The sitrans DTM needs at least one installed device description to function properly. Please install the missing device description(s) before trying to use the DTM. This has been installed on Pactware V4.0 and 4.1 and on 3 different PC's in our plant, neither of them can get to work. Glenn. |
4/29/2016 2:23 PM | |
Joined: 12/13/2012 Last visit: 10/5/2023 Posts: 124 Rating: (45)
|
Dear Glenn , Maybe you should contact pactware here directly ? FAQ: http://www.pactware.com/en/faq.htmlhttp://www.pactware.com/en/faq.html Question : It happens after start-up that DTMs which have been installed recently are not listed in the device catalogue ==> After a new DTM installation the device catalogue must be updated manually. Support : info@pactware.com |
11/9/2016 6:36 PM | |
Joined: 8/21/2014 Last visit: 9/19/2024 Posts: 1024 Rating: (14) |
New question published by djzam is split to a separate thread with the subject TM LR250 HART not working in PACTware 5.0 and Fieldmate 3.0.. Best regards |